Function Group "Diagnostics" (0A) - Pepperl+Fuchs Pulscon LTC Description Of Instrument Functions

Guided level radar with hart/4 ma ... 20 ma and profibus pa
Table of Contents

Advertisement

Pulscon LTC

Function group "diagnostics" (0A)

+
E
58
11
Function group "diagnostics" (0A)
In the "diagnostics" function group, you can display and confirm error messages.
Type of error
Errors that occur during commissioning or measuring are displayed immediately on the
local display. If two or more system or process errors occur, the error with the highest
priority is the one shown on the display.
The measuring system distinguishes between two types of error:
A (Alarm):
Instrument goes into a defined state (e. g. MAX)
Indicated by a constant
(For a description of the codes, see page 72)
W (Warning):
Instrument continue measuring, error message is displayed.
Indicated by a flashing
(For a description of the codes, see page 72)
E (Alarm/Warning):
Configurable (e. g. loss of echo, level within the safety distance)
Indicated by a constant/flashing
(For a description of the codes, see page 72)
Error messages
Error messages appear as four lines of plain text on the display. In addition, a unique
error code is also output. A description of the error codes is given on page 72.
The "diagnostics" (0A) function group can display current errors as well as the last
errors that occurred.
If several current errors occur, use
The last occurring error can be deleted in the "diagnostics" (0A) function group
with the function "clear last error" (0A2).
symbol.
symbol.
symbol.
O
S
to page through the error messages.