Function "Determine Length" (034); Function "Empty Calibr." (005); Empty Calibr - Pepperl+Fuchs Pulscon LTC Description Of Instrument Functions

Guided level radar with hart/4 ma ... 20 ma and profibus pa
Table of Contents

Advertisement

Pulscon LTC
Function group "basic setup" (00)
3.9
+
E
Use this function, the probe length can be determined automatically.
Due to the mounting conditions, the automatically determined probe length may be
larger than the actual probe (typically 20 mm ... 30 mm longer). This has no influence on
the measuring accuracy. When entering the empty value for a linearisation, please use
the "empty calibration" instead of the automatically determined probe length.
Selection:
length ok
too short
too long
After selection "too short" or "too long", the calculation of the new value need approx.
10 s.
3.10
+
E
This function is used to enter the distance from the flange (reference point of the
measurement) to the minimum level (= zero).
E

Function "determine length" (034)

Function "empty calibr." (005)

0 %
E = empty calibration (= zero)
E
= probe length – lower blocking distance
max
17