System Error Messages - Pepperl+Fuchs Pulscon LTC Description Of Instrument Functions

Guided level radar with hart/4 ma ... 20 ma and profibus pa
Table of Contents

Advertisement

Pulscon LTC
Trouble-shooting
Code
Description
A102
checksum error
general reset & new calibr. required
W103
initialising - please wait
A106
downloading please wait
A110
checksum error
general reset & new calibr. required.
A111
electronics defect
A113
electronics defect
A114
electronics defect
A115
electronics defect
A116
download error
repeat download
A121
electronics defect
W153
initialising - please wait
A160
checksum error
general reset & new calibr. required.
A164
electronics defect
A171
electronics defect
A221
probe pulse deviation from average
values
A241
broken probe
A251
feedthrough
A261
HF cable defective
W275
offset too high
W512
recording of mapping please wait
W601
linearisation ch1 curve not monotone
W611
less than 2 linearisation points for
channel 1
W621
simulation ch. 1 on
E641
no usable echo
channel 1
check calibr.
W650
signal/noise ratio too low or no echo
E651
level in safety distance - risk of
overspill
A671
linearisation ch1 not complete, not
usable
W681
current ch1 out of range
72
15.2

System error messages

Possible cause
device has been powered off before
data could be stored;
EMC problem; E
2
E
PROM storage not yet finished
processing data download
device has been powered off before
data could be stored;
EMC problem; E
RAM defective
ROM defective
2
E
PROM defective
general hardware problem
checksum of stored data not correct
no factory calibration existant;
2
E
PROM defective
initialisation of electronics
device has been powered off before
data could be stored;
EMC problem; E
hardware problem
hardware problem
HF module or cable between HF
module and electronics defective
broken probe or value for probe
length is too short
broken probe detection is activated,
without carry out the mapping before
lost contact in the process
feedthrough
HF cable defective or HF connector
removed
temperature at the electronics too
high or HF module defective
mapping active
linearisation not monotonously
increasing
number of entered linearisation
points < 2
simulation mode is active
echo lost due to application
conditions of built up on antenna
noise on signal to high
level in safety distance
linearisation table is in edit mode
current out of range
(3.8 mA ... 21.5 mA)
Remedy
reset
avoid EMC problem;
2
PROM defect
if alarm prevails after reset, exchange electronics
wait some seconds; if warning prevails, exchange
electronics
wait until warning disappears
reset
avoid EMC problem;
2
PROM defect
if alarm prevails after reset, exchange electronics
reset
if alarm prevails after reset, exchange electronics
reset
if alarm prevails after reset, exchange electronics
reset
if alarm prevails after reset, exchange electronics
reset
if alarm prevails after reset, exchange electronics
restart download of data
contact service
wait some seconds; if warning prevails, power off
device and power on again
reset
avoid EMC problem;
2
PROM defect
if alarm prevails after reset, exchange electronics
reset
if alarm prevails after reset, exchange electronics
reset
if alarm prevails after reset, exchange electronics
check contacts on HF module
if fault cannot be eliminated: replace HF module
check the probe length in 033, check the probe
itself, if the probe is broken, change the probe, or
change to a non contact system
deactivate broken probe detection; carry out
mapping; activate broken probe detection
replace process feedtrough
check HF connector, replace cable if defective
check temperature, replace HF module if defective
wait some seconds until alarm disappears
correct linearisation table
correct linearisation table
switch off simulation mode
check installation; clean probe (see operating
instructions)
eliminate electromagnetic interference
alarm will disappear as soon as level leaves safety
distance
activate linearisation table
check calibration and linearisation