Function Group "Basic Setup" (00); Function "Measured Value" (000); Function "Tank Properties" (002); Function 000 = Measured Value - Pepperl+Fuchs Pulscon LTC Description Of Instrument Functions

Guided level radar with hart/4 ma ... 20 ma and profibus pa
Table of Contents

Advertisement

Pulscon LTC

Function group "basic setup" (00)

3
+
E
3.1
+
E
This function displays the current measured value in the selected unit
(see "customer unit" (042)) function). The number of digits after decimal point can be
selected in the "no.of decimals" (095) function.
3.2
+
E
This function is used to select the tank properties.
Selection:
standard
aluminium tank
plastic tank
bypass/pipe
coax probe
concrete wall
standard
The "standard" option is recommended for normal containers for rod and rope probes.
aluminium tank
The "aluminium tank" option is designed especially for high aluminium silos that cause
an increased level of noise when empty. This option is only useful for probes longer than
4 m. For short probes (< 4 m) select the "standard" option!
Note!
!
If "aluminium tank" is selected, the device calibrates of its own accord when first filled,
depending on the medium's properties. Slope errors can, therefore, occur when
beginning the first filling procedure.
plastic tank
Select the "plastic tank" option when installing probes in wood or plastic containers
without metallic surfaces at the process connection (see installation in plastic
containers). When using a metallic surface at the process connection, the "standard"
option is sufficient!
Note!
!
In principle the employment of a metallic surface area should be preferred at the
process connection!
Function group "basic setup" (00)

Function "measured value" (000)

Function "tank properties" (002)

13