Pulscon LTC
Function group "basic setup" (00)
–
+
E
!
–
+
E
–
+
E
16
3.6
Function "probe length" (031)
Use this function to select whether the probe length was changed after factory
calibration. Only then is it necessary to enter or correct the probe length.
Selection:
•
modified
•
not modified
Note!
If "modified" was selected in the "probe length" (031) function, the probe length is
defined in the next step.
3.7
Function "probe" (032)
Use this function to select whether the probe is at the time of the commissioning
uncovered or covered.
If the probe is uncovered, the Pulscon can determine the probe length automatically
"determine length" (034) function. If the probe is covered, a correct entry is required in
the "probe length" (033) function.
Selection:
•
free
•
covered
3.8
Function "probe length" (033)
Use this function, the probe length can be entered manually.