Function group "diagnostics" (0A)
"
–
+
E
60
11.4
Function "reset" (0A3)
Caution!
A reset sets the instrument back to the factory settings. This can lead to an impairment
of the measurement. Generally, you should perform a basic setup again following a
reset.
A reset is only necessary:
•
if the instrument no longer functions
•
if the instrument must be moved from one measuring point to another
•
if the instrument is being de-installed/put into storage/installed
Entry ("reset" (0A3)):
•
333 = customer parameters (HART)
•
33333 = customer parameters (PROFIBUS PA)
333 = reset customer parameters for HART
33333 = reset customer parameters for PROFIBUS PA
This reset is recommended whenever an instrument with an unknown "history" is to be
used in an application:
•
The Pulscon LTC is reset to the default values.
•
The customer specific tank map is not deleted.
•
A linearisation is switched to "linear" although the table values are retained. The
table can be reactivated in the "linearisation" (04) function group.
List of functions that are affected by a reset:
•
tank properties (002)
•
medium cond. (003)
•
process proper. (004)
•
empty calibr. (005)
•
full calibr. (006)
•
output on alarm (010)
•
output on alarm (011)
•
outp. echo loss (012)
•
ramp %span/min (013)
•
delay time (014)
•
safety distance (015)
•
in safety dist. (016)
•
overspill protection (018)
•
end of probe (030)
•
level/ullage (040)
•
linearisation (041)
•
customer unit (042)
The mapping can also be deleted in the "cust. tank map" (055) function of the
"extended calibr." (05) function group.
A complete "basic setup" (00) must be activated.
•
max. scale (046)
•
diameter vessel (047)
•
check distance (051)
•
range of mapping (052)
•
start mapping (053)
•
offset (057)
•
output damping (058)
•
low output limit (062)
•
curr. output mode (063)
•
fixed cur. value (064)
•
4mA value (068)
•
language (092)
•
back to home (093)
•
format display (094)
•
no of decimals (095)
•
sep. character (096)
•
unlock parameter (0A4)