Function "safety settings" (01)
–
+
E
–
+
E
22
4
Function "safety settings" (01)
4.1
Function "output on alarm" (010)
This function is used to select the reaction of output on an alarm.
Selection:
•
MIN (<= 3.6mA)
•
MAX (22mA)
•
Hold
•
User specific
MIN (<= 3.6mA)
HART
(110 %)
[mA]
22
(-10 %)
3.6
If the instrument is in alarm state, the output changes as follows:
•
HART:
•
PROFIBUS PA:
MAX 110% 22mA
HART
[mA]
(110 %)
22
(-10 %)
3.6
If the instrument is in alarm state, the output changes as follows:
•
HART:
•
PROFIBUS PA:
-99999
t
MIN-Alarm 3.6 mA
MIN-Alarm -99999
+99999
t
MAX-Alarm 22 mA
MAX-Alarm +99999
PA
t
PA
t