Function "Ramp %Span/Min" (013) - Pepperl+Fuchs Pulscon LTC Description Of Instrument Functions

Guided level radar with hart/4 ma ... 20 ma and profibus pa
Table of Contents

Advertisement

Pulscon LTC
Function "safety settings" (01)
hold
On echo loss, a warning is generated after a definable "delay time" (014). Output is
held.
ramp %/min
On echo loss, a warning is generated after a definable "delay time" (014). The output is
changed towards 0 % or 100 % depending on the slope defined in
"ramp %span/min" (013).
4.4
+
E
Ramp slope which defines the output value on echo loss. This value is used if
"ramp %span/min" is selected in "outp. echo loss" (012). The slope is given in % of
the measuring range per minute.
Δ %

Function "ramp %span/min" (013)

25