M51, Motor Reactor Terminal Connection - Siemens SINAMICS S120 Device Manual

Cabinet modules nema
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

8.41

M51, Motor reactor terminal connection

Availability of option
This option is available for the following S120 Cabinet Modules:
● Booksize Cabinet Kits
Description
In connection with option M77 (version without component support plates and without
additional control components), option L08/L09 (motor reactor / 2 motor reactors in series)
allows the motor cables to be connected directly to the motor reactor.
With option M51, the connection of the motor cable is wired to a customer connection
terminal -X1.
Table 8- 63
Order no.
6SL3720-
1TE21-0AB3
1TE21-8AB3
1TE23-0AB3
1TE24-5AB3
1TE26-0AB3
1TE28-5AB3
1TE31-3AB3
Cabinet Modules NEMA
Manual, 04/2014, A5E03586450A
Maximum conductor cross-section when using motor reactors for Booksize Cabinet Kits
Power in kW (HP)
4.8 (5)
9.7 (10)
16 (20)
24 (30)
32 (40)
46 (60)
71 (100)
8.41 M51, Motor reactor terminal connection
Maximum conductor cross-
section in mm² (AWG)
6 (10)
6 (10)
6 (10)
16 (6)
16 (6)
35 (2)
95 (4/0)
Options
489