7.10
LEDs on the Voltage Sensing Module (VSM) in the Active Interface
Module
Table 7- 19
Meaning of the LEDs on the Voltage Sensing Module in the Active Interface Module
LED
Color
---
Green
Orange
Red
RDY
(READY)
Green/
Red
Green/
Orange
or
Red/
Orange
Cabinet Modules NEMA
Manual, 04/2014, A5E03586450A

7.10 LEDs on the Voltage Sensing Module (VSM) in the Active Interface Module

Status
Description
Off
The electronics power supply is missing or lies outside the permissible tolerance
range.
Continu-
The component is ready for operation and cyclic DRIVE-CLiQ communication is
ous light
taking place.
Continu-
DRIVE-CLiQ communication is being established.
ous light
Continu-
At least one fault is present in this component.
ous light
Note:
LED is activated irrespective of any reconfiguring of the corresponding messages.
Flashing
Firmware is being downloaded.
0.5 Hz
Flashing
Firmware download is being completed.
2 Hz
Waiting for POWER ON.
Flashing
Detection of the component via LED is activated (p0144).
2 Hz
Note:
The two options depend on the LED status when component detection is activated
via p0144 = 1.