Note
Power supply for the digital inputs
In the circuit example, the power for the digital inputs (terminals -X122 and -X132) is
supplied from the internal 24 V voltage of the Control Unit (terminal -X124).
The two groups of digital inputs (optocoupler inputs) each have a common reference
potential (reference ground M1 or M2). To close the circuit when the internal 24 V supply is
used, the reference grounds M1 / M2 are connected to internal ground (M).
If power is not supplied from the internal 24 V supply (terminal -X124), the jumper between
grounds M1 and M or M2 and M must be removed in order to avoid potential current loops.
The external ground must then be connected to terminals M1 and M2.
8.20.4

X55 customer terminal block

8.20.4.1

Overview

Description
Figure 8-27
Cabinet Modules NEMA
Manual, 04/2014, A5E03586450A
Option G55, customer terminal block -X55
8.20 K90, Control Unit CU320-2 DP
Options
401