8.6

G56, Contactor monitoring

Availability of option
This option is available for the following S120 Cabinet Modules:
● Basic Line Modules
● Smart Line Modules
● Active Line Modules
Description
The option is used for monitoring the pre-charging and bypass contactors of the Line
Modules.
The connecting cable from the contactors to the Control Interface Module is factory-installed.
Activation
The monitoring is activated using the following parameters:
● p0255.0 = monitoring time for the pre-charging contactor (factory setting = 0, max.
6500 ms)
● p0255.1 = monitoring time for the bypass contactor (factory setting = 0, max. 6500 ms)
Fault messages
● F30060 (A) pre-charging contactor status monitoring
● F30061 (A) bypass contactor status monitoring
8.7

K01 to K05, safety license for 1 to 5 axes

Availability of option
This option is available for the following S120 Cabinet Modules:
● Booksize Cabinet Kits
● Motor Modules in chassis format
Description
The Safety Integrated Basic functions do not require a license. A license is, however,
required for each axis with safety functions in the case of Safety Integrated Extended
functions. It is irrelevant which safety functions are used and how many.