Electrical installation
4.5 Connections
Cable routing to the customer terminal block -X55
1. Feed the cable for the customer terminal block into the cabinet from the bottom left.
2. Remove about 1.18 inch (3 cm) of the cable insulation at the level of the shield plate in
the lower part of the cabinet and attach the cable there.
3. To secure the cable in accordance with EMC requirements, snap the clip onto the shield
plate.
4. Use cable ties to secure the cable at suitable points.
5. Feed the cable toward the top of the cabinet and, when it reaches the level of the
customer terminal block -X55, guide it to the left or right to -X55. When doing so, route
the cable in a similar manner to the standard cables that have already been installed in
the cabinet.
6. Use cable ties to secure the cable at suitable points.
7. Connect the cables to the customer terminal block -X55.
110
Frame size:
FB
GB, GD
Cabinet Modules NEMA
Manual, 04/2014, A5E03586450A