Technical Specifications - Siemens SINAMICS S120 Device Manual

Cabinet modules nema
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Options
8.34 L61/L62, L64/L65, braking units
Thermostatic switch
Table 8- 55
Terminal
T1
T2
Max. connectable cross-section #16 AWG (1.5 mm²)
Risk of death from fire when thermostatic switch evaluation is not available
When evaluation of the thermostatic switch is not available, there is a risk of fire leading to
death or serious injury.
• If you evaluate the thermostatic switch by the Control Unit or a higher-level controller, a
8.34.7

Technical specifications

Load data for the braking units
Table 8- 56
Load data for the braking units
Line voltage
Braking
Module
continuous
power
P
DB
380 ... 480 V
25 kW
380 ... 480 V
50 kW
500 ... 600 V
50 kW
660 ... 690 V
25 kW
660 ... 690 V
50 kW
472
Thermostatic switch connection
Function
Thermostatic switch connection
Thermostatic switch connection
WARNING
shutdown must be performed, if necessary.
Braking
Module
peak power
P
15
125 kW
250 kW
250 kW
125 kW
250 kW
Braking Module
Braking Module
P
power
P
power
20
40
100 kW
50 kW
200 kW
100 kW
200 kW
100 kW
100 kW
50 kW
200 kW
100 kW
Braking resistor
Max. current
R
B
4.4 Ω ± 7.5%
189 A
2.2 Ω ± 7.5%
378 A
3.4 Ω ± 7.5%
306 A
9.8 Ω ± 7.5%
127 A
4.9 Ω ± 7.5%
255 A
Cabinet Modules NEMA
Manual, 04/2014, A5E03586450A