Table 7- 9
Meaning of the OPT LED on the Control Unit
LED
Color
OPT
–
Green
Red
Orange
Cabinet Modules NEMA
Manual, 04/2014, A5E03586450A
Status
Description, cause
OFF
Electronics power supply is missing or outside the permissi-
ble tolerance range.
Communication Board either defective or not inserted.
Continu-
Communication Board is ready and cyclic communication is
ous light
taking place.
Flashing
The Communication Board is ready, but cyclic communica-
0.5 Hz
tions is not running.
Possible causes:
At least one fault is present.
•
Communication is being established.
•
Continu-
Cyclic communication via PROFINET has not yet been
ous light
established. However, acyclic communication is possible.
SINAMICS is waiting for a parameter assign-
ment/configuration message frame.
Flashing
The firmware update into the CBE20 has been completed
0.5 Hz
with an error.
Possible causes:
The CBE20 is defective.
•
The memory card for the control unit is defective.
•
In this state, the CBE20 cannot be used.
Flashing
There is a communication error between the Control Unit
2 Hz
and the CBE20.
Possible causes:
The board was removed following power-up.
•
The board is defective.
•
Flashing
Firmware is being updated.
0.5 Hz
7.4 LEDs on the CBE20 Communication Board
Diagnostics
Remedy
–
–
–
–
–
Correctly insert the
board, if required,
replace.
–
337