8.16 K76, auxiliary voltage generating unit in the Line Connection Module

8.16
K76, auxiliary voltage generating unit in the Line Connection Module
Availability of option
● Line Connection Modules
Description
Cabinet Modules require an auxiliary energy supply to function properly. This current
demand must be included in the configuration and supplied from an external source. If an
external supply is not possible, the required auxiliary voltages can be generated by an
Auxiliary Power Supply Module.
Alternatively, option K76 can be selected to generate the auxiliary voltages in the Line
Connection Module. This is particularly advisable for smaller device configurations.
The following auxiliary voltages are available:
● 2 AC 380 to 480 V or 500 to 690 V
possible tap for the following Line Connection Modules:
– Line Connection Module with rated current up to 800 A: 28 ... 40 A
– Line Connection Module with rated current greater than 800 A: 60 A
● 230 V AC (poss. tap approx. 4 ... 6 A)
● 24 V DC (poss. tap approx. 20 ... 40 A)
The auxiliary voltages in the Line Connection Module can be connected to the auxiliary
power module therefore supplying the complete cabinet group.
If the Cabinet Modules are delivered as factory-assembled transport units (option Y11), the
electrical installation work has already been carried out.
If the parts are delivered individually, the auxiliary power supply interface must be installed
with 3 cables on site.
Depending on the version, the power loss is approx. 100 W.
Adapting the auxiliary power supply (-T10)
A transformer is integrated in the Line Connection Module (-T10) for the 230 V AC auxiliary
voltage supply of the cabinet. The location of the transformer is indicated in the layout
diagrams supplied.
When delivered, the taps are always set to the highest level. The line-side terminals of the
transformer may need to be reconnected according to the existing line voltage.
390
Cabinet Modules NEMA
Manual, 04/2014, A5E03586450A