8.11 K50, Sensor Module Cabinet-Mounted SMC30
X521/X531 encoder connection 2 for HTL/TTL/SSI encoder with open-circuit monitoring
Table 8- 13
Encoder connection X521
Terminal
1
2
3
4
5
6
7
8
Max. connectable cross-section #16 AWG (1.5 mm²)
Note
Operation of unipolar HTL encoders
When unipolar HTL encoders are used, terminal block A*, B*, and R* must be jumpered with
M encoder (-X531).
Table 8- 14
Encoder connection X531
Terminal
1
2
3
4
5
6
7
8
max. connectable cross-section #16 AWG (1.5 mm²)
When using unipolar HTL encoders, at the terminal block A*, B*, R* must be connected to (jumper) M_Encoder (X531)
Because the physical transmission media is more robust, the bipolar connection should always be used. The unipolar
1)
connection should only be used if the encoder type does not output push-pull signals.
384
Signal name
A
A*
B
B*
R
R*
CTRL
M
Signal name
P encoder 5 V/24 V
M encoder
-Temp
+Temp
Clock
Clock*
Data
Data*
Technical specifications
Incremental signal A
Inverted incremental signal A
Incremental signal B
Inverted incremental signal B
Reference signal R
Inverted reference signal R
Control signal
Ground
Technical specifications
Encoder supply
Ground, encoder supply
Motor temperature measurement KTY84-1C130 (KTY-)
Temperature sensor KTY84-1C130/PTC/
bimetallic switch with NC contact
SSI clock
Inverted SSI clock
SSI data
Inverted SSI data
1)