X41 Ep Terminal / Temperature Sensor Connection - Siemens SINAMICS S120 Device Manual

Cabinet modules nema
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Cabinet Modules
5.6 Motor Modules in chassis format
Description
The customer interface -X55 is available in the cabinet irrespective of the CU320-2 Control
Unit. Terminal blocks -X41 and -X46 are assigned by default.
With option K90/K95, terminal blocks -X122 and -X132 are also fully assigned
(→ see "Options", section "K90, Control Unit CU320-2 DP" or section "K90, Control Unit
CU320-2 PN")
Note
Interfaces -X1, -X2, -X3, and -X4 are wired within the cabinet and are not available for
customer connections!
If the customer terminal block is ever replaced, connectors -X1 and -X2 must not be
interchanged! Otherwise, the "Safe Torque Off" and "Safe Stop 1" safety functions will
malfunction.
5.6.2.2

X41 EP terminal / temperature sensor connection

Table 5- 33
Terminal strip X41 EP terminals / temperature sensor connection
Terminal
1
2
3
4
Max. connectable cross-section: #14 AWG (2.5 mm
Risk of death from electric shock in the event of voltage flashovers at the temperature
sensor
Voltage flashovers in the signal electronics can occur in motors without safe electrical
separation of the temperature sensors.
• Only use temperature sensors that fully comply with the specifications of the electrical
• If safe electrical separation cannot be guaranteed (for linear motors or third-party
222
Function
EP M1
(enable pulses)
EP +24 V
(enable pulses)
- Temp
+ Temp
WARNING
separation.
motors, for example), use a Sensor Module External (SME120 or SME125) or the
Terminal Module TM120.
Technical specifications
Supply voltage: 24 V DC (20.4 to 28.8 V)
Current consumption: 10 mA
Signal propagation times:
L → H: 100 μs;
H → L: 1000 μs
The pulse inhibit function is only available when Safety Integrated Basic
Functions are enabled.
Temperature sensor connection for motor temperature measurement:
KTY84-1C130, PTC, PT100, bimetallic switch with NC contact
)
2
Cabinet Modules NEMA
Manual, 04/2014, A5E03586450A

Advertisement

Table of Contents
loading