Options
8.11 K50, Sensor Module Cabinet-Mounted SMC30
For encoders with a 5 V supply at X521/X531, the cable length is dependent on the encoder
current (this applies to cable cross-sections with #20 AWG (0.5 mm²)):
Figure 8-18
Signal cable length as a function of the encoder current consumption
For encoders without Remote Sense, the permissible cable length is restricted to 330 ft
(100 m) (reason: The voltage drop depends on the cable length and the encoder current).