8.22 K95, CU320-2 PN Control Unit
Note
Connection cables
The PROFINET interfaces support Auto MDI(X). It is therefore possible to use both crossed
and uncrossed cables to connect the devices.
For diagnostic purposes, the two PROFINET interfaces are each equipped with a green and
a yellow LED. These LEDs indicate the following status information:
Table 8- 38
LED states of the X150 P1/P2 PROFINET interface
LED
Color
Link port
-
Green
Activity port
-
Yellow
8.22.9

T0, T1, T2: Measuring sockets

Table 8- 39
PCB plug connector from Phoenix Contact, type: ZEC 1.0/ 4-ST-3.5 C1 R1.4, order number: 1893708
Note
Cable cross-section
The measuring socket contacts are only suitable for cable cross-sections of 0.2 mm
1 mm
Note
Use of the measuring socket contacts
The measuring socket contacts are used to support commissioning and diagnostics. It must
not be connected for normal operation.
434
State
Description
Off
Missing or faulty link
Continuous
10 or 100 Mbit link available
light
Off
No activity
Flashing
Data is being received or sent at port x
light
Measuring sockets T0, T1, T2
Socket
T0
T1
T2
M
.
2
Function
Measuring socket 0
Measuring socket 1
Measuring socket 2
Ground
Technical specifications
Voltage: 0 ... 5 V
Resolution: 8 bits
Load current: max. 3 mA
Continued-short-circuit-proof
The reference potential is terminal M
Cabinet Modules NEMA
Manual, 04/2014, A5E03586450A