Table 4- 4
X100, terminal block for tapping the auxiliary voltages
Terminal
1
2
3
4
5
6
The maximum load-carrying capacity of the auxiliary power supply system is 80 A according to IEC (or 80 A according to
UL).
Max. connectable cross-section: #14 AWG (2.5 mm
Max. total current of all tapping terminals available
1)
Table 4- 5
X101, terminal block for routing the auxiliary voltage connecting cables
Terminal
1
2
3
4
5
6
The maximum load-carrying capacity of the auxiliary power supply system is 80 A according to IEC (or 80 A according to
UL).
Max. connectable cross-section: #2 AWG (35 mm
Tightening torque: 2 Nm (max. 30 lb-in)
Note
The connection is only permitted with copper cables.
The use is only permitted in environments with degree of pollution II in accordance with IEC
61800-5-1.
Cabinet Modules NEMA
Manual, 04/2014, A5E03586450A
Designation
Voltage tap
L1
Line voltage (for fan supply via transformer):
L2
380 to 480 V 2 ph. AC
500 to 690 V 2 ph. AC (max. 759 V AC)
L1
230 V 1 ph. AC (max. 265 V AC)
N
P24
24 V DC for the electronics power supply
(max. 30 V DC)
M
)
2
Designation
Assigned voltages
L1
Line voltage (for fan supply via transformer):
L2
380 to 480 V 2 ph. AC
500 to 690 V 2 ph. AC (max. 759 V AC)
L1
230 V 1 ph. AC (max. 265 V AC)
N
P24
24 V DC for the electronics power supply
(max. 30 V DC)
M
)
2
Electrical installation
4.5 Connections
Rated current
Max. 16 A
1)
Max. 16 A
1)
Max. 10 A
1)
Rated current
Max. 60 A
Max. 80 A
Max. 80 A
81