3 | Description
Tab. 7: Cable plugs for single cable connection (interface type A)
Cable type
Cable plugs
Make
Thermoplastic-insulated cables ≤ 12 kV according to IEC/EN 60502-2 / VDE 0276-620
1-core cable, PE- and XLPE-
Nexans Euromold
insulated N2YSY (Cu) and
N2XSY (Cu)
or
NA2YSY (Al) and
NA2XSY (Al)
nkt cables
Südkabel
Cooper Power Sys-
tems
Prysmian Kabel und
Systeme (Pirelli Elek-
trik)
3M Deutschland
TE Connectivity
Thermoplastic-insulated cables 15 / 17.5 / 24 kV according to IEC / EN 60502-2 / VDE 0276-620
1-core cable, PE- and XLPE-
Nexans Euromold
insulated N2YSY (Cu) and
N2XSY (Cu)
or
NA2YSY (Al) and
NA2XSY (Al)
nkt cables
Südkabel
Cooper Power Sys-
tems
Prysmian Kabel und
Systeme (Pirelli Elek-
trik)
3M Deutschland
TE Connectivity
1)
G = straight cable plug, W = cable elbow plug

3.8.4 Single cable connection with voltage transformer 4MT8 (interface type C)

20/174
Type
158LR
152SR
200LR
K200LR-12
K200SR-12
EASW 10 / 250, size
2
EASG 10 / 250, size 2 G
CE 24 – 250
SEHDG 11.1
SEW 12
DE 250 – R-C
DS 250 – R-C
FMCE-250
93-EE 605-2 / -95
93-EE 600-2 / xx
RSSS 52xx
RSES 52xx-R
K158LR
K152SR
200LR
K200LR-16
K200SR-16
EASG 20 / 250
CE 24 – 250
SEHDG 21.1
SEW 24
DE 250 – R-C
DS 250 – R-C
FMCE-250
93-EE 605-2 / -95
93-EE 600-2 / xx
RSSS 52xx
RSES 52xx-R
The voltage transformer 4MT8 can be installed in ring-main feeders and circuit-breaker feeders
with a panel width of 500 mm. A deep cable compartment cover is not necessary.
For connection, symmetrical cable T-plugs (see table) are required. Before performing a voltage
test at the cables (on site with max. 80% U
8DJH • Installation and Operating Instructions • Version 11 • 500-8384.9
1)
Conductor
Design
G/W
cross-section
2
[mm
]
W
16...120
screened; with capacitive measuring point
G
95...120
screened; with capacitive measuring point
W
25...95
screened; with capacitive measuring point
W
25...95
screened
G
25...95
screened
W
25...95
screened; option: with metal housing or capacitive
measuring point
25...95
screened; option: with capacitive measuring point
W
95...120
screened; option: with metal housing or capacitive
measuring point
G
25...120
screened; option: with metal housing
W
25...120
screened; option: with metal housing
W
16...120
screened
G
16...120
screened
W
25...120
screened
W
25...95
screened; option: with metal housing
G
25...150
screened; option: with metal housing
G
25...95
screened; with capacitive measuring point
W
25...120
screened; with capacitive measuring point
W
16...120
screened; with capacitive measuring point
G
25...120
screened; with capacitive measuring point
W
25...95
screened; with capacitive measuring point
W
25...95
screened
G
25...95
screened
G
25...95
screened; option: with metal housing
W
25...95
screened; option: with metal housing or capacitive
measuring point
G
25...70
screened; option: with metal housing
W
25...95
screened; option: with metal housing
W
16...120
screened
G
16...120
screened
W
25...120
screened
W
25...95
screened; option: with metal housing
G
25...150
screened; option: with metal housing
G
16...70
screened; with capacitive measuring point
W
16...120
screened; with capacitive measuring point
), the voltage transformers must be removed.