Printed Circuit Board For Rpi-(8.0-20.0)Fsn3(P)E(-F) Units (Pi065-Pi005) - Hitachi RCI-1.0FSR Service Manual

Hide thumbs Also See for RCI-1.0FSR:
Table of Contents

Advertisement

4 Control system

Printed circuit board for RPI-(8.0-20.0)FSN3(P)E(-f) units (PI065-PI005)

4.7 Printed circuit board for RPI-(8.0-20.0)FSN3(P)E(-f) units (PI065-PI005)
YX2
YX5
YX4
R
X2
X5
X4
84
SMGB0137 rev.0 - 05/2021
YX3
CN404
CN403
CN402
CN401
X3
LED indicator
This LED indicates the transmission
LED1
Red
status between the indoor unit and
the remote control.
This LED indicates the transmission
LED3
Yellow
status between the indoor unit and
the outdoor unit.
LED4
Red
PCB power supply
PCB1 Connector indication
PCN1
220 V transformer
PCN2
Internal thermostat for indoor fan motor
PCN3
Fan stoppage alarm signal
PCN6
Drain pump motor (RPI)
PCN7
Terminal board - Power supply
THM1
Air inlet thermistor
THM2
Air outlet thermistor
THM3
Liquid pipe thermistor
Optional connector (for remote temperature
THM4
sensor)
THM5
Gas pipe thermistor
EFR1
Power supply fuse
EF1
Fuse for PCN5 connector
EF4
PCB fuse
CN1
Transformer (20 V)
Terminal board - H-LINK control circuit and
CN2
remote control switch
CN3
Optional input functions
CN7
Optional output functions
CN8
Optional output functions
CN11
Printed circuit board 2 (CN401)
CN17
Printed circuit board 2 (CN404)
CN14
Float switch (RPI)
PCB2 Connector indication
CN401
Printed circuit board 1 (CN11)
CN404
Printed circuit board 1 (CN17)
CN402
Expansion valve control
CN403
Expansion valve control
YX2
Relay for High speed (Terminal X2)
YX5
Relay for S-Low speed (Terminal X5)
YX4
Relay for Low speed (Terminal X4)
YX3
Relay for Medium speed (Terminal X5)
R
Terminal board - Fan motor power supply
Switch indication
DSW3
Capacity code
DSW4
Unit model code
DSW5,
Refrigerant cycle number setting
RSW2
DSW6,
Indoor unit number setting
RSW1
DSW7
Fuse recovery and remote control selector