Hitachi RCI-1.0FSR Service Manual page 268

Hide thumbs Also See for RCI-1.0FSR:
Table of Contents

Advertisement

7 Servicing
RPK-FSR(H)M - Wall mounted
6 Removing Inlet Air Thermistor
a. The inlet air thermistor is fixed to the receiver PCB holder cover under the electrical box.
Its wire runs the back of the receiver PCB holder and enters into the electrical box from the opening for wires on 
the bottom of the electrical box.  Detach two catches on the back of the receiver PCB holder cover to dismount 
the holder cover.  Remove the thermistor fixed into two grooves on the receiver PCB holder cover.
b.  When to attach inlet air thermistor, take the reverse steps of it.  Care to not get the wire caught between the 
receiver PCB holder cover and the receiver PCB holder.  The risk runs of wire disconnection.
c. After attaching the thermistor, clamp the wiring for the expansion valve, freeze protection thermistor, gas pipe 
thermistor and inlet air thermistor with 1 plastic band.
Inlet air thermistor
Receiver PCB Holder Cover
Inlet at lower side of Electrical Box
7 Removing Outlet Air Thermistor
a.
Remove the front panel according to the "7.7.2 Removal of the front
b.  Lift the front side of the vertical blade up in the direction of the arrow to remove it.
c. Remove 1 screw fixing the outlet air thermistor cover to remove the cover.
Outlet air thermistor
Outlet Air Thermistor
258
SMGB0137 rev.0 - 05/2021
Receiver PCB holder
(When Receiver PCB Holder Cover was removed.)
Vertical blade
Screw fixing cover for 
outlet air thermistor
Catches on receiver PCB 
holder cover (2 Portions)
(Reverse Side of Receiver PCB Holder)
Fix in the position 
where the head of 
the thermistor fits 
into this space.
panel" chapter.
Outlet air thermistor
Cover for outlet air thermistor
Approx 
29mm