Hitachi RCI-1.0FSR Service Manual page 122

Hide thumbs Also See for RCI-1.0FSR:
Table of Contents

Advertisement

5 Optional functions
Optional functions through Remote control
Element
Optional function
Prevention of low air
outlet temperature in
cooling mode
Models:
RPI-(4.0-6.0)FSRE
d4
Not used
Models:
RCD-FSR
RPI-(0.4-3.0)FSRE
RCI-FSR
RPC-FSR
RCIM-FSRE
RPF(I)-FSN2E
RPI-(8~20)FSN3(P)E
Prevention of low air
outlet temperature in
d5
heating mode
Room temperature control
d6
for energy saving
Econofresh: Minimum
opening angle of the
d7
outdoor air (OA) damper
112
SMGB0137 rev.0 - 05/2021
Individual
Settings
setting
Function disabled
00
(factory setting)
O
Function enabled
01
00
O
-
01
Function disabled
00
(factory setting)
O
Function enabled
01
Function disabled
00
(factory setting)
O
Function activated
01
6º (factory setting)
00
12º
01
18º
02
24º
03
O
30º
04
36º
05
42º
06
48º
07
Setting conditions
This function is used to prevent
the decrease of discharge
air temperature in cooling
operation, by controlling
Thermo-ON/OFF according to
the discharge air temperature.
When ambient temperature >
setting temperature:
If air outlet temperature ≤ 11 ºC
for 3 minutes, the system is
switched to Thermo-OFF.
In this status, if air outlet
temperature ≥ 13 ºC, the system 
is switched back to Thermo-ON.
Use at 00 conditions
This function prevents the
occurrence of an excessively
cold air flow in heating mode 
by decreasing the fan speed
during heating operation, also
taking into account the setting of
function C5.
This function saves energy
when the outdoor temperature
is lower than the air conditioning
load.
The indoor unit is set to cooling
Thermo-OFF when:
Tout (outside ambient
temperature - out of the building)
< Tin
This function is used to set the
minimum opening angle of the
damper for fresh outdoor air.
Description