5 Optional functions
Optional functions through Remote control
Element
Optional function
Automatic OFF timer
setting
Models:
RCI-FSR
RPC-FSR
RPK-FSRM
RPI(L/H)-FSRE
RCD-FSR
RCIM-FSRE
RPI-FSN3(P)E
F1
Automatic OFF timer
setting
Models:
RPF(I)-FSN2E
Remote control main-sub
F2
setting
Automatic reset of setting
F3
temperature
Automatic reset time
F4
115
SMGB0137 rev.0 - 05/2021
Individual
Settings
setting
Function disabled
00
(Factory setting)
1 hour
01
2 hours
02
3 hours
03
(04-24) hours
04-24
X
30 minutes
0A
90 minutes
0B
40 minutes
0C
45 minutes
0D
50 minutes
0E
55 minutes
0F
Function disabled
00
(Factory setting)
1 hour
01
2 hours
02
X
3 hours
03
(04-24) hours
04-24
30 minutes
0A
90 minutes
0B
Main (Master remote control)
00
(Factory setting)
X
Sub (Slave remote control)
01
Function disabled
00
(Factory setting)
X
Function enabled
01
30 minutes (factory setting)
00
15 minutes
01
X
60 minutes
02
90 minutes
03
Setting conditions
This function sets an automatic
OFF timer to switch OFF the
indoor units controlled by the
remote control switch (when
the units have been started by
remote control).
}
(Do not set the values "0C"-
"0F" when two remote control
switches are used in the same
Do not set these
remote control group)
when two wired
controllers are
used.
This function is used to set the
automatic timer to switch off 
when the unit has been started
by remote control.
This function is used to define 
which remote control switch is
used as master or slave, when
two remote controllers are
connected to one indoor unit.
This function is used to limit unit
operation and save energy.
The setting temperature is
automatically set to the value
defined with functions "F5" or 
"F6", according to the current 
operation mode, after the time
set with function "F4" has 
passed since the last manual
change of setting temperature.
In case that the values of "F5" 
or "F6" are out of the limits set 
with functions "FC" and "Fd", 
limitations set by "FC" and "Fd" 
have priority.
This function sets the automatic
reset time delay for function F3.
Description
5