5 Optional functions
Optional functions through Remote control
Item
Optional function
Operation of the
louvres in energy-
L3
saving Thermo-OFF
(Cooling / Dry mode)
Fan acceleration
in energy-saving
L4
Thermo-OFF
(Cooling mode)
Louvre swing
operation during
L5
energy-saving
forced Thermo-OFF
Not used
L6
Not available
L7
Not used
L8
Not used
Lg
Not used
LA
Not used
Lb
Setting temperature
P1
in 0.5 ºC steps
Not used
P2
Temperature sensor
P3
displayed
Display of sensor
P4
temperature
Display of setting
temperature when
P5
operation mode is
Fan
153
SMGB0137 rev.0 - 05/2021
Individual
Settings
Setting
00
Direct air blow Low (factory setting)
01
Direct air blow Medium
02
Direct air blow High
03
Disabled
Function disabled
00
(factory setting)
01
Function enabled
Function disabled
00
(factory setting)
01
Function enabled
00
-
-
01
"- -"
-
permanent
00
-
-
01
00
-
01
00
-
-
01
00
-
-
01
Enabled (0.5 °C steps)
00
(factory setting)
×
01
Disabled (1 °C steps)
00
-
-
01
00
Inlet air thermistor (Tin)
01
Outdoor air thermistor (Tout)
×
02
Remote controller thermistor (RCS)
03
Remote sensor (THM4)
00
Hidden
×
01
Shown
00
Shown
×
01
Hidden
Setting conditions
Power save must be ON in order to
use this function (L5 must be set to
01).
This function is used to establish
louvre swinging operation ranging
from continuous swing to static
operation.
Low: Continuous louvre swing
Medium: Louvre swing with
intermittent stops for 20/40 seconds
High: Louvre stopped at full opening
position, according to the setting of
CF.
This function increases fan speed
by one step to prevent the loss of
comfort due to the forced Thermo-
OFF for energy saving during
cooling operation.
This function is used to enabled the
setting of function L3.
Use at 00 conditions
Use at 00 conditions
Use at 00 conditions
Use at 00 conditions
Use at 00 conditions
This function is used to define 
whether setting temperature is
adjusted in 0.5 ºC steps (when set
to "00") or in 1 ºC steps (when set
to "01").
This setting also determines whether
the resolution of temperature
differential of the thermistor is 0.5 ºC 
(when set to "00") or 1 ºC (when set
to "01").
Use at 00 conditions
This function is used to select the
thermistor whose temperature is
shown when function P4 is set to 01.
This function is used to display the
temperature of the sensor selected
with function P3.
This function is used to hide the
display of setting temperature during
operation in fan mode.
Description