5 Optional functions
Optional functions through Remote control

5.2.3 Optional functions for PC-ARH1E remote controls

Item
Optional function
Heating temperature
compensation
Models:
RCI-FSR
RCIM-FSRE
RCD-FSR
RPC-FSR
RPI(L/H)-FSRE
b1
RPI-FSN3E(P)E(-f)
RPK-FSR(H)M
Heating temperature
compensation
Models:
RPF(I)-FSN2E
Circulation function
at heating
b2
Thermo-OFF
Not Used
b3
Change of filter 
b4
cleaning period
Locking of operation
mode
b5
(Not available for
models KPI-E4)
Locking of setting
b6
temperature
Setting operation
mode as cooling
only.
b7
(Not available for
models KPI-E4)
Automatic COOL/
HEAT operation.
b8
(Not available for
models KPI-E4)
142
SMGB0137 rev.0 - 05/2021
Individual
Settings
Setting
Normal (factory setting)
00
(Setting Temperature + 4 ºC)
No compensation
01
(Setting Temperature)
02
Setting Temperature + 2 ºC
03
Setting Temperature + 3 ºC
04
Setting Temperature + 1 ºC
RPF(I)-FSN2E: Normal
00
(factory setting)
(Setting Temperature + 2 ºC)
No compensation
01
(Setting Temperature)
02
Setting Temperature + 2 ºC
Function disabled
00
(factory setting)
01
Function enabled
00
-
-
01
00
Standard (1200 hours)
01
100 hours
1200 hours
02
(factory setting)
03
2500 hours
04
No indication
Function disabled
00
(factory setting)
×
01
Function enabled
Function disabled
00
(factory setting)
×
01
Function enabled
Function disabled
00
(factory setting)
×
01
Function enabled
00
Function disabled (factory setting)
×
01
Function enabled
Setting conditions
This function is used to adjust the
temperature difference between the 
temperature read by the inlet sensor
and the real room temperature.
This is useful when the inlet air
thermistor is not placed inside the
indoor unit or due to uneven heat
load.
?
This function keeps the fan running
during the Thermo-OFF sequence,
at the fan speed set on the remote
control switch, to prevent the
stratification of air in the room.
Use at 00 conditions
This function is used to modify the
period of operation after which the
air filter cleaning indication is shown 
in the remote control.
For RPK-FSR(H)M models, the
factory setting is b4=00: Standard
setting 200 hours.
This function prevents the
modification of the operation mode 
of the unit from the remote controller
and from central controls, once it
has been selected.
This function prevents the
modification of the setting 
temperature of the unit from the
remote controller and from central
controls, once it has been selected.
This function is used to limit the
operation mode to cooling only and
to prevent heating mode from being
enabled.
This function enables the selection
of Auto cool/heat operation mode.
If the function is not activated, Auto
cool/heat mode cannot be selected
on the remote control switch.
Description
N O T E
The "02", "03", "04" settings may
not be available depending on
the type of indoor unit.
This setting shall be performed
separately for each indoor unit,
even in case that multiple indoor
units are connected to one
remote controller.