Removing Heat Exchanger - Hitachi RCI-1.0FSR Service Manual

Hide thumbs Also See for RCI-1.0FSR:
Table of Contents

Advertisement

7 Servicing
RPK-FSR(H)M - Wall mounted

7.7.9 Removing heat exchanger

!
D A N G E R
TURN OFF all power source switches.
!
C A U T I O N
Recover the refrigerant from the unit before the work. After all the refrigerant is recovered, turn OFF all power source switches.
Make sure that the unit will not be damaged. If having difficulty in performing the work alone, the work shall be taken by two people.
Take special care not to be injured by the heat exchanger fins.

For RPK-(0.4-1.5)FSR(H)M
1 Remove the power source wiring, the transmission wiring and the wiring for the remote control switch.
2 Push the portion indicated by "PUSH" on the underside of the unit to release the catches at the lower part of the unit.
3 Remove the flare nuts attached to the rear piping of the heat exchanger to disconnect the pipings. Then lift the indoor 
unit up and draw it frontward to remove it.
4
Remove the front panel according to the "7.7.2 Removal of the front
5
Remove the electrical box according to the "7.7.7 Removing AS
6
Remove the drain pan according to the "7.7.8 Removing drain
Catch for bottom side of indoor unit
"PUSH"
253
SMGB0137 rev.0 - 05/2021
panel" chapter.
motor" chapter.
pan" chapter.
Mounting
plate
Piping holder
Rear piping of heat exchanger
Rear side of indoor unit
Connected 
pipings
7

Hide quick links: