Electrical Connection Of Rpi Units - Hitachi RCI-1.0FSR Service Manual

Hide thumbs Also See for RCI-1.0FSR:
Table of Contents

Advertisement

3 Electrical and control settings
Unit electrical wiring and connection
Follow the steps below to connect the earth wire to the earth connection in the electrical box:
1 Where necessary, loosen the screw on the earthing connection in the electrical box.
2 Connect the shielded part of the power supply earth wire and the signal wiring earth wire to the earth connection.
3 Tighten the screw on the earthing connection in the electrical box.
4 Check that the shielded part of the earthing cables are correctly secured.
1
Electrical box
2
Tie
3
Die-cut wiring hole
4
Grille
5
Remote control wiring (optional)
6
Communication wiring
7
Power wiring
Remote control
Power supply wires
(PC-ARFP1E)
Transmission
wires
Test runs
!
C A U T I O N
Be careful during the test runs, as some of the safety functions remain disabled: the units operate for two hours without switching off
via the thermostat. The three-minute compressor protection is not enabled during the test.
Secure the rubber bushes to the panel using adhesive when the outdoor unit ducts are not used.
The compressor remains at a standstill during forced stoppage.

3.1.6 Electrical connection of RPI units

Work prior to the electrical connection
1 Turn off the power supply switches before starting work and fit the appropriate locks and safety warnings.
2 Wait 5 minutes after turning off the power supply switches.
3 Check that the fans on the indoor and outdoor units are at a standstill before starting work.
?
N O T E
The electrical power for the unit must involve a specific power line, with an exclusive power control switch and residual current breaker,
installed in line with local or national safety regulations.
Check that the electrical power line has enough capacity to supply the unit. Its length, the cable diameter and their protection (sleeve
or jacket) must be appropriate for the unit.
For further information, always consider the current regulations in the country where the unit is to be installed.
!
C A U T I O N
Risk of fire: cables must never touch the refrigerant pipes, printed circuit boards (PCB), sharp edges or electrical components inside
the unit to avoid damaging them.
Loose connection terminals may lead to cable and terminal overheating. The unit may operate incorrectly, leading to a risk of fire.
Check that the cables are firmly secured to the connection terminals.
45
SMGB0137 rev.0 - 05/2021
Part
(single phase)
Earth screw
Cord clamps
Electrical box
Knockout hole
for wirings
Grille