5 Optional functions

Optional functions through Remote control

5.2 Optional functions through Remote control
The next list refers to the optional functions available to indoor units from the remote control switch. Note that not all
remote control switch have access to all the optional functions. Check the remote control switch technical documentation
for detailed information.

5.2.1 List of optional remote control functions (PC-ARFP1E)

Element
Optional function
Heating temperature
compensation
Models:
RCI-FSR
RCIM-FSRE
RCD-FSR
RPC-FSR
RPI(L/H)-FSRE
b1
RPI-FSN3E(P)E(-f)
RPK-FSR(H)M
Heating temperature
compensation
Models:
RPF(I)-FSN2E
Circulation function at
b2
heating Thermo-OFF
Forced compressor
operation for at least three
minutes
b3
(Not available for models
KPI-E4)
Change of filter cleaning 
b4
period
Locking of operation
mode
b5
(Not available for models
KPI-E4)
Locking of setting
b6
temperature
107
SMGB0137 rev.0 - 05/2021
Individual
Settings
setting
Normal (factory setting)
00
(Setting Temperature + 4 ºC)
No compensation
01
(Setting Temperature)
O
Setting Temperature + 2 ºC
02
Setting Temperature + 3 ºC
03
Setting Temperature + 1 ºC
04
RPF(I)-FSN2E: Normal
(factory setting)
00
(Setting Temperature + 2 ºC)
O
No compensation
01
(Setting Temperature)
Setting Temperature + 2 ºC
02
Function disabled
00
(factory setting)
O
Function enabled
01
Function disabled (factory setting):
Forced compressor operation for at
00
least three minutes can be enabled or
disabled through C7 setting
O
Function enabled:
Forced compressor operation for at
01
least three minutes always occurs
independently of C7 setting
Standard (1200 hours)
00
100 hours
01
1200 hours
O
02
(factory setting)
2500 hours
03
No indication
04
Function disabled
00
(factory setting)
X
Function enabled
01
Function disabled
00
(factory setting)
X
Function enabled
01
Setting conditions
This function is used to adjust
the temperature difference 
between the temperature read
by the inlet sensor and the real
room temperature.
This is useful when the inlet air
thermistor is not placed inside
the indoor unit or due to uneven
heat load.
?
This function keeps the fan
running during the Thermo-OFF
sequence, at the fan speed set
on the remote control switch, to
prevent the stratification of air in 
the room.
This function is used to allow
the setting of C7, to protect the
compressor by preventing it
from being started or stopped for
periods of less than 3 minutes.
This function is used to modify
the period of operation after
which the air filter cleaning 
indication is shown in the remote
control.
For RPK-FSR(H)M models,
the factory setting is b4=00:
Standard setting 200 hours.
This function prevents the
modification of the operation 
mode of the unit from the remote
controller and from central
controls, once it has been
selected.
This function prevents the
modification of the setting 
temperature of the unit from
the remote controller and from
central controls, once it has
been selected.
Description
N O T E
The "02", "03", "04" settings
may not be available
depending on the type of
indoor unit.
This setting shall be
performed separately for
each indoor unit, even in
case that multiple indoor
units are connected to one
remote controller.
5