Hitachi RCI-1.0FSR Service Manual page 130

Hide thumbs Also See for RCI-1.0FSR:
Table of Contents

Advertisement

5 Optional functions
Optional functions through Remote control
Element
Optional function
Louvre swing operation
during energy-saving
L5
forced Thermo-OFF
Not used
L6
Not available
L7
Not used
L8
Not used
L9
Not used
LA
Not used
Lb
Setting temperature in 0.5
P1
ºC steps
Not used
P2
Temperature sensor
P3
displayed
Display of sensor
P4
temperature
Display of setting
temperature when
P5
operation mode is Fan
Operation of the ECO
P6
button
Prohibition of menu
P7
screen transition
Not used
P8
Not used
P9
Daylight saving time
PA
120
SMGB0137 rev.0 - 05/2021
Individual
Settings
setting
Function disabled
00
(factory setting)
O
Function enabled
01
00
-
-
01
"- -"
permanent
00
-
-
01
00
-
-
01
00
-
-
01
00
-
-
01
Enabled (0.5 °C steps)
00
(factory setting)
X
Disabled (1 °C steps)
01
00
-
-
01
Inlet air thermistor (Tin)
00
Outdoor air thermistor (Tout)
01
X
Remote controller thermistor (RCS)
02
Remote sensor (THM4)
03
Hidden
00
X
Shown
01
Shown
00
X
Hidden
01
ECO button enabled (factory setting)
00
X
ECO button disabled
01
Function disabled
00
(factory setting)
X
Function enabled
01
00
-
-
01
00
-
-
01
1 hour
00
X
2 hours
01
Setting conditions
This function is used to enabled
the setting of function L3.
Use at 00 conditions
Use at 00 conditions
Use at 00 conditions
Use at 00 conditions
Use at 00 conditions
This function is used to define 
whether setting temperature is
adjusted in 0.5 ºC steps (when
set to "00") or in 1 ºC steps
(when set to "01").
This setting also determines
whether the resolution of
temperature differential of the 
thermistor is 0.5 ºC (when set to
"00") or 1 ºC (when set to "01").
Use at 00 conditions
This function is used to
select the thermistor whose
temperature is shown when
function P4 is set to 01.
This function is used to display
the temperature of the sensor
selected with function P3.
This function is used to hide the
display of setting temperature
during operation in fan mode.
The operation of ECO button is
disabled when P6 is set to 01
This function is used to prohibit
the access to the menu screens.
The text "Display disabled" 
appears on screen instead.
Use at 00 conditions
Use at 00 conditions
This function is used to set the
amount of adjustment when
daylight saving time is applied.
Description

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents