CONTROL SYSTEM
9
/6
9.2.

INDOOR UNIT PCB

9.2.1.

PRINTED CIRCUIT BOARD LAYOUT (EXCEPT RPK)

n
PCB drawing
The PCB in the Indoor Unit is operating with 4 types of
DIP Switches, 1 sliding Switch and 1 Rotary Switch. The
location is as follows:
CONNECTOR INDICATION
PCN1
Transformer (220V)
PCN2
Internal Thermostat Indoor Fan Motor
PCN3
Electric Heater
Electric Heater for dew protection
PCN5
((SR Heater) RPC & Panel)
PCN6
Drain Pump Motor (RCI/RPI)
PCN7
Power Source (1-R, 2-S, 3-N, 4-E)
PCN8
Capacitor
PCN10
Fan Motor Power
PCN11
Fan Motor Speeds control
THM1
Inlet Air
THM2
Outlet Air
THM3
Liquid Pipe
THM4
Remote Thermistor (THM-R2 AE)
THM5
Gas Pipe
LED's INDICATION
LED1
Green
LED2 Yellow
LED3
Red
CONNECTOR INDICATION
CN1
Transformer (pin 1-2: 17.3V / pin 3-4: 20.8V)
CN2
Control Circuit for OUTDOOR UNIT H-Link
CN3
Input optional functions (only 2)
CN7
Output optional functions (only 2)
CN8
Output optional functions (#1 #2, only 1)
CN11
Expansion Valve Control
CN12
Remote control Bridge connector for multiple units
CN13
Remote control SW
CN14
Float Switch (RCI/RPI)
CN17
Swing Louver Motor
DSW3
Capacity Code
DSW5
REF. Cycle Nº
DSW6
Model Code
DSW7
Fuse Recover and Remote Control Selector
RSW
Setting of indoor unit number
SSW
Selector SW (PC-2H2/PC-P1HE)
Power Source for PCB
This LED indicates the
transmission state between
Indoor Unit and RCS
This LED indicates the
transmission state between
the indoor unit and outdoor
unit