7 Servicing
RPK-FSR(H)M - Wall mounted
For RPK-(2.0-4.0)FSRM
1 Remove the electrical box according to the "Removing Electrical Box" chapter.
2 Put Philips screw driver from the air outlet opening. Unscrew the screws that connect the fan and the fan motor. The
Philips screw driver goes straight against the cutout of the fan.
?
N O T E
The fan motor can be taken out even if the screws are not perfectly disconnected.
3 Detach three screws that fix the motor support
4 Disconnect the catch of the motor support A out of the body. Pull the motor support A out.
262
SMGB0137 rev.0 - 05/2021
Put philips screwdriver from the air outlet opening
View of Fan from Air Outlet Opening
Catch of motor support A
Motor support
screw
Fan motor
(3 positions)
Fan screw
Cutout of fan
Put out the motor support A downward
Motor
support A