Code Description
2108 START INHIBIT
Sets the Start inhibit function on or off. The Start inhibit function ignores a pending start command in any of the
following situations (a new start command is required):
• A fault is reset.
• Run Enable (parameter 1601) activates while start command is active.
• Mode changes from local to remote.
• Control switches from
• Control switches from
0 =
– Disables the Start inhibit function.
OFF
1 =
– Enables the Start inhibit function.
ON
2109 EMERG STOP SEL
Defines control of the Emergency stop command. When activated:
• Emergency stop decelerates the motor using the emergency stop ramp (parameter 2208
• Requires an external stop command and removal of the emergency stop command before drive can restart.
0 =
– Disables the Emergency stop function through digital inputs.
NOT SEL
1 =
1 – Defines digital input
DI
• Activating the digital input issues an Emergency stop command.
• De-activating the digital input removes the Emergency stop command.
2...6 =
2...
6 – Defines digital input
DI
DI
• See
1 above.
DI
-1 =
1(
) – Defines an inverted digital input
DI
INV
• De-activating the digital input issues an Emergency stop command.
• Activating the digital input removes the Emergency stop command.
-2...-6 =
2(
)...
6(
DI
INV
DI
• See
1(
) above.
DI
INV
2110 TORQ BOOST CURR
Sets the maximum supplied current during torque boost.
See parameter 2101
2113 START DELAY
Defines the Start delay. After the conditions for start have been fulfilled, the drive waits until the delay has elapsed
and then starts the motor. Start delay can be used with all start modes.
• If
=
START DELAY
ZERO
• During the start delay, alarm 2028
Start-Up
Supplied from China by: Guangzhou Tofee Electro Mechanical Equipment Co., Ltd
Email: info@tofee.com.cn
1 to
2.
EXT
EXT
2 to
1.
EXT
EXT
1 as the control for Emergency stop command.
DI
2...
6 as the control for Emergency stop command.
DI
DI
1 as the control for Emergency stop command.
DI
) – Defines an inverted digital input
INV
.
START FUNCTION
, the delay is disabled.
START DELAY
2...
6 as the control for Emergency stop command.