ABB ACS510-01 User Manual page 187

Low voltage ac drives
Table of Contents

Advertisement

ACS510 User's Manual
Bit
5
6
7
8...9
10
11
12...15 Unused
Status Word
As described earlier in "Control Interface", the contents of the
information, sent by the drive to the master station. The following table and the state
diagram later in this sub-section describe the status word content.
Bit
0
1
2
3
Supplied from China by: Guangzhou Tofee Electro Mechanical Equipment Co., Ltd
Email: info@tofee.com.cn
ABB Drives Profile (FBA)
Name
Value
RAMP_HOLD
1
RFG OUT ENABLED
0
RFG OUT HOLD
RAMP_IN_
1
RFG INPUT ENABLED
ZERO
0
RFG INPUT ZERO
RESET
0=>1
RESET
0
OPERATING
Unused
REMOTE_CMD
1
0
EXT CTRL LOC
1
EXT
0
EXT
ABB Drives Profile (FBA)
Name
Value
RDY_ON
1
0
RDY_RUN
1
0
RDY_REF
1
0
TRIPPED
0...1
0
CONTROL WORD
Commanded
State
Enable ramp function.
Enter
RAMP FUNCTION GENERATOR
ACCELERATOR ENABLED
Halt ramping (Ramp Function Generator
output held)
Normal operation. Enter
Force Ramp Function Generator input to
zero.
Fault reset if an active fault exists (Enter
-
SWITCH
ON INHIBITED
.
COMM
Continue normal operation
Fieldbus control enabled
= /
• CW
Ref.
• CW = 0 and Ref = 0: Fieldbus control
enabled.
• Ref and deceleration/acceleration ramp
are locked.
2
Select external control location 2 (
SELECT
Effective if 1102 =
1
Select external control location 1 (
SELECT
Effective if 1102 =
STATUS WORD
Description
(Correspond to states/boxes in the state diagram)
READY TO SWITCH ON
NOT READY TO SWITCH ON
READY TO OPERATE
1
OFF
ACTIVE
OPERATION ENABLED
OPERATION INHIBITED
FAULT
No fault
Comments
:
OPERATING
). Effective if 1604 =
= /
0 or Ref
0: Retain last CW and
EXT
.
COMM
EXT
.
COMM
is status
STATUS WORD
Fieldbus Adapter
187
2).
1).