ABB ACS510-01 User Manual page 66

Low voltage ac drives
Table of Contents

Advertisement

66
Group 01: Operating Data
This group contains drive operating data, including actual signals. The drive sets the
values for actual signals, based on measurements or calculations. You cannot set
these values.
Code Description
0101 SPEED & DIR
The calculated signed speed of the motor (rpm). The absolute value of this parameter is the same as the value of
0102
.
SPEED
• The value is positive if the moter runs in the forward direction.
• The value is negative if the moter runs in the reverse direction.
0102 SPEED
The calculated speed of the motor (rpm).
0103 OUTPUT FREQ
The frequency (Hz) applied to the motor. (Shown by default in the control panel OUTPUT mode.)
0104 CURRENT
The motor current, as measured by the ACS510. (Shown by default in the control panel OUTPUT mode.)
0105 TORQUE
Output torque. Calculated value of torque on motor shaft in % of motor nominal torque. (Shown by default in the
control panel OUTPUT mode.)
0106 POWER
The measured motor power in kW.
0107 DC BUS VOLTAGE
The DC bus voltage in V DC, as measured by the ACS510.
0109 OUTPUT VOLTAGE
The voltage applied to the motor.
0110 DRIVE TEMP
The temperature of the drive power transistors in degree Celsius.
0111 EXTERNAL REF 1
External reference,
REF
0112 EXTERNAL REF 2
External reference,
REF
0113 CTRL LOCATION
Active control location. Alternatives are:
0 =
LOCAL
1 =
1
EXT
2 =
2
EXT
0114 RUN TIME (R)
The drive's accumulated running time in hours (h).
Can be reset by pressing UP and DOWN keys simultaneously when the control panel is in the Parameters mode.
0115 KWH COUNTER (R)
The drive's accumulated power consumption in kilowatt hours.
Can be reset by pressing UP and DOWN keys simultaneously when the control panel is in the Parameters mode.
0116 APPL BLK OUTPUT
Application block output signal. Value is from either:
• PFC control, if PFC Control is active, or
• Parameter 0112
EXTERNAL REF
Start-Up
Supplied from China by: Guangzhou Tofee Electro Mechanical Equipment Co., Ltd
Email: info@tofee.com.cn
1, in Hz.
2, in %.
2.
ACS510 User's Manual

Hide quick links:

Advertisement

Table of Contents
loading