ABB ACS560 Quick Installation And Start-Up Manual

ABB ACS560 Quick Installation And Start-Up Manual

Standard control program
Hide thumbs Also See for ACS560:

Advertisement

ABB GENERAL PURPOSE DRIVES
ACS560 standard control program
Quick installation and start-up guide
English . . . . . . . 3
हिं द ी . . . . . . . . 129
3AXD50000042620 Rev H MUL
EFFECTIVE: 2020-08-17
EN
HI

Advertisement

Table of Contents
loading

Summary of Contents for ABB ACS560

  • Page 1 — ABB GENERAL PURPOSE DRIVES ACS560 standard control program Quick installation and start-up guide English ..3 हिं द ी ..129 3AXD50000042620 Rev H MUL EFFECTIVE: 2020-08-17...
  • Page 3: En - Quick Installation And Start-Up Guide

    EN - Quick installation and start-up guide This guide instructs how to install and start-up the ACS560 drive of all frame sizes (R0...R8). For complete information, see the drive ACS560 standard control program firmware manual (3AXD50000044997[English]) and ACS560 drives (0.75 to 160 kW, 1.0 to 215 hp) hardware manual (3AXD50000044998[English]).
  • Page 4: Protect The Drive And Input Power Cable

    4 EN - Quick installation and start-up guide • 40 °C (+104 °F) for R3...R8 frames No condensation or frost is allowed. For more information on the ambient temperature, see the hardware manual. ■ Protect the drive and input power cable If you use gG fuses, make sure that the operating time of the fuse is below 0.5 seconds.
  • Page 5: Install The Drive

    EN - Quick installation and start-up guide 5 Install the drive You can install the drive • to a DIN installation rail with integrated lock. This method applies to frames R0...R2 only. • with screws to a suitable surface (wall or assembly plate). This method applies to all frames R0...R8.
  • Page 6 6 EN - Quick installation and start-up guide ■ Installing a drive with screws (frames R0...R8) All drives of frames R0...R8 can be installed on a wall with screws. See the required screw sizes in below mounting dimensions table. See also Dimensions, weights and free space requirements (page 103) WARNING!
  • Page 7 EN - Quick installation and start-up guide 7 See the example of mounting screws in frame R0 6. Frames R5...R8 only: Remove the front cover with fastening screws (6a), move the cover to the top side (6b) and then up (6c). 7.
  • Page 8 Use a measuring voltage of 1000 V DC. The insulation resistance of an ABB motor must be more than 100 Mohm (reference value at 25 C [77°F]). For the insulation resistance of other motors, refer to the manufacturer’s instructions.
  • Page 9: Connecting The Power Cables

    EN - Quick installation and start-up guide 9 Connecting the power cables ■ Connection diagram For alternatives, see hardware manual. Use a separate grounding PE cable (2a) or a cable with a separate PE conductor (2b) if the conductivity of the shield does not meet the requirements for the PE conductor (see hardware manual). 360°...
  • Page 10: Connection Procedure: Frames R0

    10 EN - Quick installation and start-up guide ■ Connection procedure: frames R0…R2 If the drive is connected on an IT (ungrounded) system, make sure that the EMC filter and Varistor (VAR) is disconnected. For more information, see hardware manual. 1.
  • Page 11 EN - Quick installation and start-up guide 11 3. Connect the motor cable as follows: • Ground the shield 360° by tightening the clamp of the power cable grounding shelf onto the stripped part of the cable (3a). • Connect the twisted shield of the cable to the grounding terminal (3b). •...
  • Page 12: Input Power Cable

    12 EN - Quick installation and start-up guide Input power cable 4. Prepare the ends of the cable as illustrated in the figure. Note: The bare shield will be grounded 360°. Mark the pigtail made from the shield as a PE conductor with yellow-and-green color 5.
  • Page 13 EN - Quick installation and start-up guide 13 9. Tighten the screws to the torque given below. Frame size R0…R1 N·m lbf·ft N·m lbf·ft UDC+/R+, R- 0.5…0.6 1.2…1.5 0.9…1.1 Finalization 10. Ground the motor cable shield at the motor end. For minimum radio frequency interference, ground the motor cable shield 360°...
  • Page 14 14 EN - Quick installation and start-up guide ■ Connection procedure, frames R3...R4 If the drive is connected on an IT (ungrounded) system, make sure you have disconnected the EMC filter and Varistor (VAR). See EMC filter (page 29). 1. Remove the front cover as follows: •...
  • Page 15 EN - Quick installation and start-up guide 15 3. Connect the motor cable as follows: If the power cable is temporarily removed from the grounding shelf, connect the motor and input power cables except the 360° grounding, and then reinstall the grounding shelf. •...
  • Page 16 16 EN - Quick installation and start-up guide Input power cable 4. Prepare the ends of the cable as illustrated in the figure. Note: The bare shield is grounded 360°. Mark the pigtail made from the shield as a PE conductor with yellow-and-green color.
  • Page 17 EN - Quick installation and start-up guide 17 9. For R3, connect the conductors to the R+ and R- terminals (7c). 10. Tighten to the torque given below. Frame size lbf.ft R+, R- 2.5...4.5 1.8...3.3 Electrical instal Finalization Finalization 11. Install the grounding shelf for the control cables (included with the moun 11.
  • Page 18 18 EN - Quick installation and start-up guide 12. Ground the motor cable shield at the motor end. For minimum radio frequency interference, ground the motor cable shield 360° at the lead-through of the motor terminal box.
  • Page 19 EN - Quick installation and start-up guide 19 ■ Connection procedure, frames R5…R8 86 Electrical installation If the drive will be connected on an IT (ungrounded) system, make sure you have 86 Electrical installation disconnected the EMC filter and Varistor (VAR). See EMC filter (page 29).
  • Page 20 (9b). Note: Frame R8 only: • If you connected the connector to only one conductor, ABB recommends to put the conductor under the upper pressure plate. • The connectors are detachable, but ABB recommends not to detach them. If you do, detach and reinstall the connectors as follows.
  • Page 21 EN - Quick installation and start-up guide 21 M5×25/35 Frame size L1, L2, L3, T1/U, T2/V, T3/W N·m lbf·ft N·m lbf·ft N·m lbf·ft 22.1 29.5 29.5 Terminals T1/U, T2/V and T3/W • Remove the nut attached to the connector and its busbar. •...
  • Page 22 22 EN - Quick installation and start-up guide 11. Frames R8 only: If you install parallel cables, install the second grounding shelf for the parallel power cables (11a). Repeat steps 6...11 (11b). Frame R8: M5×25 M5×12 12. Install the grounding shelf of the control cables. 13.
  • Page 23: Connecting The Control Cables

    EN - Quick installation and start-up guide 23 Connecting the control cables Connect the cables as described in firmware manual. See the below default I/O connections of ABB standard macro. See other macro connections in the firmware manual.
  • Page 24 24 EN - Quick installation and start-up guide Default control connections of ABB standard macro ■ Connection diagram Note: For information of parameters listed in the diagram, see Parameter listing (page 49). Terminal sizes • (frames R0…R8): 0.14…1.5 mm (all terminals)
  • Page 25: Install Optional Modules, If Any

    BAPO-01 power extension module (for R0...R2 frames) • BIO-01 I/O extension module (for R0...R2 frames) • Fieldbus module (in frames R0...R2 frames, fieldbus module can be used with BIO-01 also) For information on supported fieldbus modules, see ACS560 product catalog.
  • Page 26: Hardware Description

    26 EN - Quick installation and start-up guide For more information on optional modules, see hardware manual. ■ Hardware description Product overview The BIO-01 front option module (Option +L515) is an I/O extension module for R0...R2 frames and can also be used with any of the fieldbus optional module. The BIO-01 I/O extension module provides: •...
  • Page 27: Electrical Installation

    ■ Install BIO-01 The BIO-01 module is automatically identified by the drive firmware. To configure the By default, RIIO-01 module is provided in ACS560 standard R0...R2 drives. You can remove inputs refer to the ACS480 firmware manual (3AXD50000047399 [English]) the RIIO-01 module and can install BIO-01 and/or fieldbus adapter module (+Fxxx).
  • Page 28: Installing Option Modules

    28 EN - Quick installation and start-up guide 132 Electrical installation c. Pull the module and remove it. Installing option modules Note: The module can be tightly in position. Note: In US deliveries, options are already installed at the factory. 3.
  • Page 29: Checking The Compatibility With It (Ungrounded) And Corner-Grounded Tn Systems

    EN - Quick installation and start-up guide 29 Checking the compatibility with IT (ungrounded) and corner-grounded TN systems ■ EMC filter The internal EMC filter is not suitable for use on an IT (ungrounded) system or on a corner-grounded TN system. Disconnect the EMC filter before connecting the drive to the supply network.
  • Page 30 30 EN - Quick installation and start-up guide Frame EMC filter Ground- to- Symmetrically Corner grounded IT systems (un- sizes phase varistor grounded TN sys- TN systems grounded or high- (EMC) tems (TN-S sys- resistance groun- (VAR) tems) ded [>30 ohms]) Drive Drive Drive...
  • Page 31: Reinstalling Covers

    EN - Quick installation and start-up guide 31 Reinstalling covers ■ Reinstalling cover, frames size R0…R2 1. Reinstall the cover. 2. Tighten the retaining screw at the bottom with a screwdriver. ■ Reinstalling covers, frame size R3, R4 1. Reinstall the module cover. Put the tabs on the cover top in their counterparts on the housing and then press the cover.
  • Page 32 32 EN - Quick installation and start-up guide ■ Reinstalling side plates and covers, frames size R5…R8 1. Reinstall the module cover. Put the tabs on the cover top in their counterparts on the housing and then press the cover. 2.
  • Page 33 EN - Quick installation and start-up guide 33 If cable conduit box is used, perform the following: Frames Action 1. Slide the cover upwards (1a) and tighten the retaining screws (1b). 2. Reinstall the module cover (2a) and press the cover at bottom. Tighten the two retaining screws (2b) with a screwdriver.
  • Page 34: Start-Up And Use

    34 EN - Quick installation and start-up guide Start up and use This section describes how to install and start-up the drive using the basic control panel. Only limited information may be available in this manual. For detailed information of all Menus and Sub menus, see the ACS-BP-S basic control panel user manual (3AXD50000032527 [English]).
  • Page 35 EN - Quick installation and start-up guide 35 Loc/Rem button – Switches between Local/Remote controls. Local control is through control panel and Remote control is through PC or external devices. ■ Display The control panel display shows the following elements: Control location and related icons: Indicates how the drive is controlled.
  • Page 36 36 EN - Quick installation and start-up guide ■ Main menu Motor data Motor control Connection macro Diagnostics Energy Efficiency Backup data Parameter settings Complete parameter list Sub menus The sub-menu items allows you to change settings and set actions. Some sub menus also have menus and/or option lists.
  • Page 37: Motor Data

    EN - Quick installation and start-up guide 37 Motor data Values in this menu are based on the motor rating plate. See parameter group 98 User motor parameters. Note: Values cannot be changed while drive is running. 1) Motor control mode 2) Motor nominal power 3) Motor nominal current 4) Motor nominal voltage...
  • Page 38 38 EN - Quick installation and start-up guide Start mode – Automatic, constant time, Fast Stop mode – Coast, Ramp Acceleration time - Time for speed to change from zero to the speed defined by parameter. Deceleration time - Time for speed to change from the speed defined by parameter to zero. Maximum frequency/ Speed - Maximum allowed frequency/speed.
  • Page 39 EN - Quick installation and start-up guide 39 Connection macro Values are based on drive type. See parameter 96.04 Macro select. Macro - Displays the selected macro name. For example, ABB standard (2-wire). I/O Connections - Displays the selected macro-specific I/O connections. See menu description below.
  • Page 40 2) 3-wire macro - Suitable when the drive is controlled using momentary push buttons. 3) ABB standard (vector) - Similar to standard macro but uses vector control. 4) Motor potentiometer - Enables adjusting the motor speed using the two-push buttons.
  • Page 41 EN - Quick installation and start-up guide 41 DI - Digital Inputs DI1...DI6 AI - Analog Inputs AI1...AI2 RO - Relay Outputs RO1...RO3 AO1 - Analog Outputs AO1...AO2 AI1 and AI2 values AO1 and AO2 values...
  • Page 42: Energy Efficiency

    42 EN - Quick installation and start-up guide Diagnostics Displays the active faults and warnings and how to fix and reset. For information about fault and warning codes, see section Diagnostics (page 111). Active Fault - Displays active faults. Fault History - Lists the fault history. Active Warnings - Displays active warnings.
  • Page 43: Backup Data

    EN - Quick installation and start-up guide 43 Backup data Restore and Backup data between drive and panel. Backup from the drive to the control panel. Restore the back up from the panel to the drive. A progress view appears during the backup. Parameter settings Contains the complete parameter list and modified parameter list.See Parameter...
  • Page 44: Setting Speed Or Frequency Reference

    44 EN - Quick installation and start-up guide Reference value: Speed (rpm) or frequency (Hz) Rotation direction: Forward or reverse Faults: Active fault code Warnings: Active warning code Setting speed or frequency reference In the Options menu , move to the speed or frequency reference (1) item using the arrow buttons. Press the OK button to open the item.
  • Page 45: Changing The Rotation Direction

    EN - Quick installation and start-up guide 45 Changing the rotation direction In the Options menu , move to the Rotational direction (2) item using the arrow buttons. Press the OK button to change the direction of motor (clockwise or counter-clockwise). View active faults/warnings In the Options menu , view active faults (3) or warnings (4).
  • Page 46 46 EN - Quick installation and start-up guide Auto configuration of I/O’s and fieldbus module You can configure the connected optional modules or/and fieldbus modules automatically. 1. Switch off the drive and connect the required modules. For more information on optional modules and its installation, see chapter Electrical installation in the hardware manual.
  • Page 47: Drive And Panel Communication Failure

    EN - Quick installation and start-up guide 47 Drive and panel communication failure The drive does not respond to the panel commands during communication failure. The drive and the panel are not compatible. Status light Continuous green Indicates that drive is functioning normally. Green, blinking Indicates an active warning in the drive.
  • Page 48 48 EN - Quick installation and start-up guide...
  • Page 49: Parameter Listing

    Parameter listing 49 Parameter listing Index Name Range/List Unit Default 01 Actual values 01.01 Motor speed used -30000.00…30000.00 01.02 Motor speed estimated -30000.00…30000.00 01.03 Motor speed% -1000.00…1000.00 01.06 Output frequency -500.00…500.00 01.07 Motor current 0.00…30000.00 01.08 Motor current% of motor nom 0.0…1000.0 01.09 Motor current% of drive nom...
  • Page 50 50 Parameter listing Index Name Range/List Unit Default 01.68 Abs motor shaft power 0.00 … 32767.00 kW or hp 03 Input references 03.01 Panel reference -100000.00 … 100000.00 0.00 03.02 Panel reference remote -100000.00 … 100000.00 0.00 03.05 FB A reference 1 -100000.00 …...
  • Page 51 Inverter temperature at fault -40...160 °C 05.88 Reference used at fault -30000.00...30000.00 0.00 05.99 BIO-01 DIP switch status Note: This feature is not available with the standard BIO-01. For information on the availability on new BIO- 01 module, contact ABB sales team.
  • Page 52 52 Parameter listing Index Name Range/List Unit Default Name 0 = OFF = DO1 on port S1, 1 = ON = AO1 on port S1 0 = OFF = DI3 on port S2 1 = ON = DO1 on port S2 2...5 Reserved 06 Control and status words...
  • Page 53 Parameter listing 53 Index Name Range/List Unit Default 06.17 Drive status word 2 0b0000...0b111 0b0000 Name Name Name Identification Safe reference 11…12 Reserved run done active Magnetized Last speed act- Start delay act- Torque control 7...8 Reserved 14...15 Reserved Speed control Jogging active Reserved Above limit...
  • Page 54 54 Parameter listing Index Name Range/List Unit Default Name Name DC hold active Motor pre-heating active Post-magnetizing active 3…15 Reserved 06.29 MSW bit 10 selection False[0], True[1], Above lim- Above limit[2] it[2], Other... 06.30 MSW bit 11 selection False[0], True[1], Ext ctrl Ext ctrl loc[2] loc[2], Other...
  • Page 55 Parameter listing 55 Index Name Range/List Unit Default 10.03 DI force selection See parameter 10.01 DI 0b0000 status. 10.04 DI force data See parameter 10.01 DI 0b0000 status. 10.05 DI1 ON delay 0.00...3000.00 0.00 10.06 DI1 OFF delay 0.00...3000.00 0.00 10.07 DI2 ON delay 0.00...3000.00...
  • Page 56 56 Parameter listing Index Name Range/List Unit Default 10.26 RO1 OFF delay 0.0 … 3000.0 10.27 RO2 source See parameter 10.24 RO1 Running [7] source 10.28 RO2 ON delay 0.0 … 3000.0 10.29 RO2 OFF delay 0.0 … 3000.0 10.30 RO3 source See parameter 10.24 RO1 Fault (-1) [15]...
  • Page 57 Parameter listing 57 Index Name Range/List Unit Default 12.13 AI1 forced value 0.000…11.000 12.15 AI1 unit selection V[2], mA[10] V[2] 12.16 AI1 filter time 0.000 … 30.000 0.100 12.17 AI1 Min 0.000…11.000 0.000 12.18 AI1 Max 0.000…11.000 10.000 12.19 AI1 scaled at AI1 Min -32768.000 …...
  • Page 58 58 Parameter listing Index Name Range/List Unit Default 13.18 AO1 source Max -32768.0 … 32767.0 50.0 13.19 AO1 out at AO1 src min 0.000 … 22.000 0.000 13.20 AO1 out at AO1 src Max 0.000 … 22.000 20.000 13.21 AO2 actual value 0.000 …...
  • Page 59 Parameter listing 59 Index Name Range/List Unit Default Not selected[0] In1P Start; In2 Stop[4] Fieldbus A[12] In1 Start[1] In1P Start; In2 Stop; In3 Dir[5] Embedded fieldbus[14] In1 Start; In2 Dir[2] In1P Start fwd; In2P Start rev; In3 Stop[6] In1 Start fwd; In2 Start rev[3] Control panel[11] 20.02 Ext1 start trigger type...
  • Page 60 60 Parameter listing Index Name Range/List Unit Default 20.19 Enable start command See parameter 20.03 Ext1 Selected[1] in1 source 20.21 Direction Request[0], Forward[1], Re- Request[2] verse[2] 20.22 Enable to rotate See parameter 20.03 Ext1 Selected[1] in1 source 20.25 Jogging enable See parameter 20.03 Ext1 Not selected[0] in1 source...
  • Page 61 Parameter listing 61 Index Name Range/List Unit Default Off[0] DI2[3] DI5[6] Supervision 2[9] Timed function 2[12] On[1] DI3[4] DI6[7] Supervision 3[10] Timed function 3[13] DI1[2] DI4[5] Supervision 1[8] Timed function Other... 1[11] 21.15 Pre-heating time delay 10...3000 21.16 Pre-heating current 0.0 …...
  • Page 62 62 Parameter listing Index Name Range/List Unit Default 22.19 Ext2 speed ref2 See parameter 22.11 Speed Zero[0] ref safe 22.20 Ext2 speed function See parameter 22.13 Ext1 Ref1[0] speed function 22.21 Constant speed function 0b0000…0b1111 0b0001 Name Name Name Constant Direction en- 2...15 Reserved...
  • Page 63 Parameter listing 63 Index Name Range/List Unit Default Disabled[0] Enabled (resume always)[2] Enabled (resume/init to Actual[4] Enabled (init at stop /power- Enable (init to actual)[3] up)[1] 22.72 Motor potentiometer initial value -32768.00 … 32767.00 0.00 22.73 Motor potentiometer up source 0...7, 18...20, 24...26 Not used[0] Not used[0]...
  • Page 64 64 Parameter listing Index Name Range/List Unit Default 24.02 Used speed feedback -30000.00…30000.00 0.00 24.03 Speed error filtered -30000.00…30000.00 0.00 24.12 Speed error filter time 0…10000 25 Speed control 25.01 Torque reference speed control -1600.0 … 1600.0 25.02 Speed proportional gain 0.00 …...
  • Page 65 Parameter listing 65 Index Name Range/List Unit Default Torque reference 1[0] DI1[3] DI4[6] Other... Torque reference 2[1] DI2[4] DI5[7] Follow Ext1/Ext2 selec- DI3[5] DI6[8] tion[2] 26.17 Torque ref filter time 0.000…30.000 0.000 26.18 Torque ramp up time 0.000…60.000 0.000 26.19 Torque ramp down time 0.000…60.000 0.000...
  • Page 66 66 Parameter listing Index Name Range/List Unit Default 28.16 Ext2 frequency ref2 See parameter 28.11 EXT1 Zero[0] frequency ref1 28.17 Ext2 frequency function See parameter 28.13 EXT1 Ref1[0] frequency function 28.21 Constant frequency function 0b0000…0b1111 0b0001 Name Name Name Constant Direction Frequency 3...15...
  • Page 67 Parameter listing 67 Index Name Range/List Unit Default Acc/Dec time 1[0] DI2[3] DI5[6] EFB DCU CW bit 10[20] Acc/Dec time 2[1] DI3[4] DI6[7] Other... DI1[2] DI4[5] FBA A [18] 28.72 Freq acceleration time 1 0.000 …1800.000 20.000 28.73 Freq deceleration time 1 0.000 …1800.000 20.000 28.74...
  • Page 68 68 Parameter listing Index Name Range/List Unit Default 30.09 Current limit monitor time 0...120 10.00 30.10 Current limit actions No action[0], Warning[1], No action[0] Fault[2] 30.11 Minimum speed -30000.00 … 30000.00 -1500.00 30.12 Maximum speed -30000.00 … 30000.00 1500.00 30.13 Minimum frequency -500.00 …...
  • Page 69 Parameter listing 69 Index Name Range/List Unit Default Zero[0] AI1 scaled[1] AI2 scaled[2] Maximum Other... speed[12] 31 Fault functions 31.01 External event 1 source 0, 1, 3...8 Inactive (true)[1] Active Inactive DI1[3] DI2[4] DI3[5] DI4[6] DI5[7] DI6[8] (false)[0] (true)[1] 31.02 External event 1 type Fault[0], Warning[1] Fault[0]...
  • Page 70 70 Parameter listing Index Name Range/List Unit Default 31.22 STO indication run/stop 0...5 Fault/Fault [0] Fault/Fault[0] Fault/Warning[1] Fault/Event[2] Warning/Warning[3]] Event/Event[4] No indication/No indication[5] 31.23 Wiring or earth fault No action[0], Fault[1] Fault[1] 31.24 Stall function No action[0], Warning[1], No action[0] Fault[2] 31.25 Stall current limit...
  • Page 71 Parameter listing 71 Index Name Range/List Unit Default 32.07 Supervision 1 signal 0, 1, 3, 4, 6...10, 23...27 Frequency[3] Zero[0] Current[4] Output power[8] Inverter temperat- Process PID set- ure[23] point[26] Speed[1] Torque[6] AI1[9] Process PID out- Process PID devi- put[24] ation[27] Frequency[3] DC voltage[7]...
  • Page 72 72 Parameter listing Index Name Range/List Unit Default 32.40 Supervision 4 high -21474836.00 … 0.00 21474836.00 32.41 Supervision 4 hysteresis 0.00...100000.00 0.00 32.45 Supervision 5 function See parameter 32.05 Super- Disabled[0] vision 1 function 32.46 Supervision 5 action No action[0], Warning[1], No action[0] Fault[2], Fault if running[3] 32.47...
  • Page 73 Parameter listing 73 Index Name Range/List Unit Default Name Name Name Season 1 Season 4 Exception holi- Season 2 4...9 Reserved 12...15 Reserved Season 3 Exception workday 34.10 Timed functions 0...7 Disabled[0] Dis- DI1[2] DI2[3] DI3[4] DI5[6] DI4[5] DI6[7] Other... abled[0] abled[1] 34.11...
  • Page 74 74 Parameter listing Index Name Range/List Unit Default 34.30 Timer 7 start time 00:00:00…23:59:59 00:00:00 34.31 Timer 7 duration 00 00:00…07 00:00 00:00:00 34.32 Timer 8 configuration See parameter 34.11 Timer 0b0111 1 configuration 34.33 Timer 8 start time 00:00:00…23:59:59 00:00:00 34.34 Timer 8 duration...
  • Page 75 Parameter listing 75 Index Name Range/List Unit Default 34.78 Exception day 4 34.79 Exception day 5 34.80 Exception day 6 34.81 Exception day 7 34.82 Exception day 8 34.83 Exception day 9 34.84 Exception day 10 34.85 Exception day 11 34.86 Exception day 12 34.87...
  • Page 76 76 Parameter listing Index Name Range/List Unit Default Disabled[0] Direct temperature[11] PTC analog I/O [20] Estimated temperature[1] KTY83 analog I/O[12] Therm(0)[21] KTY84 analog I/O[2] 1 × Pt1000 analog I/O[13] Therm(1)[22] 1 × Pt100 analog I/O[5] 2 × Pt1000 analog I/O[14] 2 ×...
  • Page 77 Parameter listing 77 Index Name Range/List Unit Default 36.12 PVL peak time 00:00:00...23:59:59 00:00:00 36.13 PVL current at peak -32768.00 … 32767.00 0.00 36.14 PVL DC voltage at peak 0.00 … 2000.00 0.00 36.15 PVL speed at peak -30000.00-30000.00 0.00 36.16 PVL reset date 1/1/1980...6/5/2159...
  • Page 78 78 Parameter listing Index Name Range/List Unit Default 40.01 Process PID output actual -200000.00 … 200000.00 0.00 40.02 Process PID feedback actual -200000.00 … 200000.00 0.00 40.03 Process PID setpoint actual -200000.00 … 200000.00 0.00 40.04 Process PID deviation actual -200000.00 …...
  • Page 79 Parameter listing 79 Index Name Range/List Unit Default Not selected[0] Motor potentiometer[8] Control panel (ref EFB ref1[19] saved)[13] Internal setpoint[2] Freq in scaled[10] Control panel (ref EFB ref2[20] copied)[14] AI1 scaled[3] AI1 percent[11] FB A ref1[15] Setpoint data stor- age[24] AI2 scaled[4] AI2 percent[12] FB A ref2[16]...
  • Page 80 80 Parameter listing Index Name Range/List Unit Default 40.44 Set 1 sleep delay 0.0 … 3600.0 60.0 40.45 Set 1 sleep boost time 0.0 … 3600.0 40.46 Set 1 sleep boost step 0.00 … 200000.00 PID unit 1 0.00 40.47 Set 1 wake-up deviation -200000.00 …...
  • Page 81 Parameter listing 81 Index Name Range/List Unit Default User text[0] inH2O[7] I/min[14] /m[21] gal/m[28] %[1] °C[8] I/h[15] /h[22] in wg[29] bar[2] °F[9] /s[16] ppm[23] MPa[30] kPa[3] mbar[10] /m[17] inHg[24] ftWC[31] Pa[4] /h[11] /h[18] kCFM[25] psi[5] /h[12] gal/s[19] inWC[26] CFM[6] I/s[13] /s[20] GPM[27] 40.80...
  • Page 82 82 Parameter listing Index Name Range/List Unit Default 41.26 Set 2 setpoint min -200000.00 … 200000.00 PID unit 1 0.00 41.27 Set 2 setpoint max -200000.00 … 200000.00 PID unit 1 200000.00 41.28 Set 2 setpoint increase time 0.0 … 1800.0 41.29 Set 2 setpoint decrease time 0.0 …...
  • Page 83 Parameter listing 83 Index Name Range/List Unit Default Off[0] Follow Ext1/Ext2 DI2[4] DI4[6] DI6[8] selection [2] On[1] DI1[3] DI3[5] DI5[7] Other... 41.79 Set 2 units See parameter 40.79 Set 1 Depends on °C[8] units selection 41.80 Set 1 PID output min source None[0], Set2 output min[1], Set2 output min[1] other...
  • Page 84 84 Parameter listing Index Name Range/List Unit Default 45.05 Saved money x1000 0…4294967295 45.06 Saved money 0.00 … 999.99 0.00 45.07 Saved amount 0.00 … 21474830.00 0.00 45.08 CO2 reduction in kilotons 0…65535 metric kiloton 45.09 CO2 reduction in tons 0.0 …...
  • Page 85 Parameter listing 85 Index Name Range/List Unit Default 46.12 Filter time output frequency 2…20000 46.13 Filter time motor torque 2…20000 46.14 Filter time power 2…20000 46.21 At speed hysteresis 0.00 … 30000.00 50.00 46.22 At frequency hysteresis 0.00 … 1000.00 2.00 46.31 Above speed limit...
  • Page 86 86 Parameter listing Index Name Range/List Unit Default Auto[0] DC voltage[7] Temp sensor 1 excita- Abs output power[31] tion[20] Motor speed used[1] Output power[8] Temp sensor 2 excita- Abs motor shaft tion[21] power[32] Output frequency[3] Speed ref ramp in[10] Abs motor speed AO1 data storage[37] used[26] Motor current[4]...
  • Page 87 Parameter listing 87 Index Name Range/List Unit Default 50.14 FBA A reference 1 -2147483648 … 2147483647 50.15 FBA A reference 2 -2147483648 … 2147483647 50.16 FBA A status word 0.0.0.0.0...FF.FF.FF.FF 0.0.0.0 50.17 FBA A actual value 1 -2147483648 … 2147483647 50.18 FBA A actual value 2 -2147483648 …...
  • Page 88 Any message[1], Cw / Ref1 / Cw / Ref1 / Ref2[2] Ref2[2] 58.16 Communication loss time 0.0…6000.0 58.17 Transmit delay 0…65535 58.18 EFB control word 0000h…FFFFh 58.19 EFB status word 0000h…FFFFh 58.25 Control profile ABB Drives[0], DCU Profile[5] ABB Drives[0]...
  • Page 89 Parameter listing 89 Index Name Range/List Unit Default 58.26 EFB ref1 type 0…5 Speed or fre- quency[0] Speed or fre- Transparent[1] General[2] Torque[3] Speed[4] Frequency[5] quency[0] 58.27 EFB ref2 type See parameter 58.26 Torque[3] 58.28 EFB act1 type See parameter 58.26 Speed or fre- quency[0] 58.29...
  • Page 90 90 Parameter listing Index Name Range/List Unit Default 70.02 Override enable Off[0], On[1] Off[0] 70.03 Override activation source 0...13 Not Used[0] Not used[0] DI2[3] DI5[6] -DI2[9] -DI5[12] Used[1] DI3[4] DI6[7] -DI3[10] -DI6[13] DI1[2] DI4[5] -DI1[8] -DI4[11] Other... 70.04 Override reference source 0...6 Override freq[3] Constant speed/freq[0]...
  • Page 91 Parameter listing 91 Index Name Range/List Unit Default 71.15 Output scaling -200000.00…200000.00 1500.00 71.16 Setpoint 1 source See parameter 40.16 Set 1 Not selected[0] setpoint 1 source. 71.19 Internal setpoint sel1 See parameter 40.19 Set 1 Not selected[0] internal setpoint sel1. 71.20 Internal setpoint sel2 See parameter 40.20 Set 1...
  • Page 92 92 Parameter listing Index Name Range/List Unit Default Name Name Name PFC 1 running PFC 3 running 4...15 Reserved PFC 2 running PFC 4 running 76.02 PFC system status 0...9, 100...103, 200...202, PFC disabled[0] 300...302, 400, 500, 600, 700, 800, 801, PFC disabled[0] PFC inactive (inval- Running with VSD...
  • Page 93 Parameter listing 93 Index Name Range/List Unit Default 76.43 Stop point 3 0…32767 76.55 Start delay 0.00…12600.00 10.00 76.56 Stop delay 0.00…12600.00 10.00 76.57 PFC speed hold on 0.00…1000.00 0.00 76.58 PFC speed hold off 0.00…1000.00 0.00 76.59 PFC contactor delay 0.20…600.00 0.50 76.60...
  • Page 94 95.04 Control board supply Internal 24V[0], External Internal 24V[0] 24V[1] 95.15 Special HW settings 0b0000…0b1111 0b0000 Name Name Name Reserved ABB Sine filter 2...15 Reserved 95.20 HW options word 1 0b0000…0b1111 0b0000 Name Name Name Name Supply fre- 1…12 Reserved du/dt filter 14…15...
  • Page 95 Done[0] PID[14] SPFC[18] Jigar[30] ABB standard[1] Panel PID[15] Pharma Application[19] 3-wire[11] PFC[16] Plastic Extrusion[20] Motor potentiometer ABB standard (vec- Torque control[28] [13] tor)[17] 96.05 Macro active See parameter 96.04 Macro ABB standard[1] select 96.06 Parameter restore 0, 2, 8, 32, 62, 512, 1024,...
  • Page 96 Disable[0] 96.100 Change user pass code 10000000…99999999 96.101 Confirm user pass code 10000000…99999999 96.102 User lock functionality 0000h…FFFFh 0000h Disable ABB access Reserved[3...5] Reserved[8...10] Disable OEM access levels[0] level 3[13] Freeze parameter lock Protect AP[6] Disable OEM access Reserved[14...15] state[1]...
  • Page 97 Parameter listing 97 Index Name Range/List Unit Default 97.08 Optimizer minimum torque 0.0...1600.0 97.13 IR compensation 0.00 … 50.00 3.50 97.20 U/F ratio Linear[0], Squared[20] Linear[0] 97.48 UDC stabilizer Disabled[0] Disabled[0] Enabled mild[100] Enabled strong[500] Enabled min[50] Enabled medium[300] Enabled max[800] 97.49 Slip gain for scalar 0...200...
  • Page 98 98 Parameter listing Index Name Range/List Unit Default 99.15 Motor polepairs calculated 0…1000 99.16 Motor phase order U V W[0], U W V[1] U V W[0]...
  • Page 99: Technical Data

    CE, UL and other approval marks. Ratings ■ IEC ratings Drive Type Nom- Max. Output ratings Frame ACS560 inal In cur- size Nominal use Light overload use Heavy-duty use rent (Con- (Con-...
  • Page 100: Ur And Ar Fuse

    100 Technical data Fuses (IEC) ■ uR and aR fuse Drive type Input cur- uR and aR Minimum ACS560 rent short cir- Rated cur- Rated Bussmann IEC 60269 cuit cur- rent I voltage designation size rent type 3 phases U = 400 V (380...480 V)
  • Page 101 Technical data 101 Drive type Input cur- gG (IEC 60269) Minimum ACS560 rent short cir- Rated cur- Rated ABB designa- IEC 60269 cuit cur- rent I voltage tion type size rent 09A4-4 15.0 OFAF000H16 12A6-4 20.2 2500 OFAF000H25 017A-4 27.2...
  • Page 102 102 Technical data Drive type Input cur- gG (IEC 60269) Minimum ACS560- rent short circuit Rated cur- Rated ABB desig- IEC 60269 current rent I voltage nation type size 106A-4 15000 170M3815 145A-4 1000 28500 170M3816 169A-4 1280 46500 170M3817...
  • Page 103: Typical Power Cable Sizes

    Technical data 103 Typical power cable sizes Drive type Frame size ACS560 Cu cable type Cu cable type AI cable type AI cable type AWG/kcmil AWG/kcmil 3-phase U = 400 V (380…480 V) 02A6-4 3 × 1.5 + 1.5 03A3-4 3 ×...
  • Page 104 104 Technical data Frame Dimensions and weight IP20 Weight 28.3 42.4 Standard frames...
  • Page 105 Technical data 105 Symbols IP20 Height of front side Height of back side (without cable connecting box) Width Depth See the detailed dimension drawings in the drive hardware manual...
  • Page 106: Applicable Standards

    106 Technical data Applicable standards The drive complies with the following standards. The compliance with the European Low Voltage Directive is verified according to standard EN 61800-5-1. EN 60204-1:2006 + AC:2010 Safety of machinery. Electrical equipment of machines. Part 1: General re- quirements.
  • Page 107: Compliance With The European Low Voltage Directive

    Technical data 107 ■ Compliance with the European Low Voltage Directive The compliance with the European Low Voltage Directive has been verified according to standard EN 61800-5-1:2007. The declaration of conformity (3AXD10000549832) is available on the Internet. See section Document library on the Internet on the inside of the back cover.
  • Page 108: Compliance With The European Emc Directive

    108 Technical data ■ Compliance with the European EMC Directive The EMC Directive defines the requirements for immunity and emissions of electrical equipment used within the European Union. The EMC product standard (EN 61800- 3:2004 + A1:2012) covers requirements stated for drives. The declaration (3AXD10000549782) is available on the Internet.
  • Page 109: Eu Declaration Of Conformity

    ■ Compliance with the European Machinery Directive 2006/42/EC 2nd Edition – June 2010 EU Declaration of Conformity Machinery Directive 2006/42/EC Manufacturer: ABB India Limited Address: Plot No 5 &6 , 2 Phase , Peenya Industrial Area ,Bangalore,560058, India Phone: +91 80 22949359...
  • Page 110 AR Madhusudhan Laxmikantha shenoy Vice President, MODP Manager , Prodcut Engineering ABB India Limited ABB India Limited 3AXD10000549832 Rev. 3 IMS template code: 3AFE011906, Rev. C The drive is a machinery component that can be integrated into a wide range of machinery categories as specified in European Commission’s Guide to application of the Machinery...
  • Page 111: Warning Messages

    Diagnostics 111 Diagnostics Warning messages Code Warning/Aux code Cause What to do (hex) (aux code visible only on assistant control panel and drive composer) 64FF Fault reset A fault has been reset. Event. Informative only. A2B1 Overcurrent Output current exceeded internal Check motor load, acceleration times, earth fault limit.
  • Page 112 Safe torque off function is active. Check safety circuit connections and para- meter 95.04 Control board supply. A5EA Measurement circuit Fault in drive internal temperat- Contact your local ABB representative. temperature ure measurement. A5EB PU board powerfail Power unit power supply failure.
  • Page 113 (aux code visible only on assistant control panel and drive composer) A5F2 Overtemperature hw Excessive hardware temperat- Contact your local ABB representative. ure. A682 Flash erase speed Flash erase speed exceeded. Avoid forcing unnecessary parameter saves by parameter 96.07 Parameter save manu- ally or cyclic parameter writes (such as user logger triggering through parameters).Check...
  • Page 114 • All switches between drive and motor are closed. • All cables between drive and motor are connected and secured. If no issue was detected and drive output was actually connected to motor, contact ABB. A791 Brake resistor Brake resistor fault. Check brake resistor. A792...
  • Page 115 Diagnostics 115 Code Warning/Aux code Cause What to do (hex) (aux code visible only on assistant control panel and drive composer) A794 BR data No brake resistor data. Check resistor data settings. A79C BC IGBT excess Brake chopper IGBT temperat- Let chopper cool down.
  • Page 116 116 Diagnostics Code Warning/Aux code Cause What to do (hex) (aux code visible only on assistant control panel and drive composer) A8B1 Signal supervision 2 Warning generated by the signal Check the source of the warning (parameter supervision function 2. 32.17 Supervision 2 signal).
  • Page 117 Diagnostics 117 Code Warning/Aux code Cause What to do (hex) (aux code visible only on assistant control panel and drive composer) A8C0 ULC invalid speed User load curve: X-axis points See parameter 37.11 ULC speed table point table (speed) are not valid. A8C5 ULC invalid under- User load curve: Underload...
  • Page 118: Fault Messages

    1081 Rating ID fault Drive software is not able to read Reset the fault or cycle the power to the the drive rating ID. drive. If the fault persists, contact your local ABB representative.
  • Page 119 Calibration Measured offset of output phase Try performing the current calibration again. current measurement or differ- If the fault persists, contact your local ABB ence between output phase U2 representative. and W2 current measurement is too great (the values are updated during current calibration).
  • Page 120 120 Diagnostics Code Fault / Aux. code Cause What to do (hex) aux code visible only on assistant control panel and drive composer)) 3381 Output phase loss Motor circuit fault due to missing Connect motor cable. motor connection (any of the If the drive is in scalar mode and nominal three phases not connected).
  • Page 121 Internal fault. Reboot the control unit using parameter Note: This fault cannot be reset. 96.08 Control board boot or by cycling power. If the problem persists, contact ABB. 6487 Stack overflow Internal fault. Reboot the control unit. If the problem per- sists, contact ABB.
  • Page 122 Operating system error. Reboot the control unit using parameter Note: This fault cannot be reset. 96.08 Control board boot or by cycling power. If the problem persists, contact ABB. 6581 Parameter system Parameter load or save failed. Try forcing a save using parameter 96.07 Parameter save manually.
  • Page 123 6686 EFB fault 3 6882 Text 32-bit table Internal fault. Reset the fault. If fault persists, contact ABB. overflow 6885 Text file overflow Internal fault. Reset the fault. If fault persists, contact ABB. The table size is too short for opening language file.
  • Page 124 Check that the acknowledgment signal (if used) matches the actual status of the brake. 7100 Excitation current Excitation current feedback low Contact your local ABB representative. or missing 7121 Motor stall Motor is operating in stall region. Check motor load, drive ratings and fault function parameters.
  • Page 125 Diagnostics 125 Code Fault / Aux. code Cause What to do (hex) aux code visible only on assistant control panel and drive composer)) 7510 FBA A communica- Cyclical communication between Check the status of fieldbus communication. tion (Programmable drive and fieldbus adapter mod- Check parameter groups 50 Fieldbus ad- fault: 50.02 FBA A ule A or between PLC and field-...
  • Page 126 126 Diagnostics Code Fault / Aux. code Cause What to do (hex) aux code visible only on assistant control panel and drive composer)) 80B0 Signal supervision 1 Fault generated by the signal Check the source of the fault (parameter supervision function 1. 32.07 Supervision 1 signal).
  • Page 127 Diagnostics 127 Code Fault / Aux. code Cause What to do (hex) aux code visible only on assistant control panel and drive composer)) 1 - Maximum current limit too low B - (Asynchronous motors only) Speed dropped to zero during ID run. 2 - Maximum speed limit or calculated field C - (Permanent magnet motors only).
  • Page 129 HI -त् व रित इं स ् ट ाले श न और स् ट ार् ट -अप गाइड This guide instructs how to install and start-up the ACS560 drive of all frame sizes (R0...R8). For complete information, see the drive ACS560 standard control program firmware manual (3AXD50000044997[English]) and ACS560 drives (0.75 to 160 kW, 1.0 to 215 hp) hardware...
  • Page 130 130 HI -त् व रित इं स ् ट ाले श न और स् ट ार् ट -अप गाइड ■ ड् र ाइव और इनपु ट पावर के ब ल की रक् ष ा करे ं यदि आप gG फ् य ू ज का उपयोग करते है ं , तो सु न िश् च ित करे ं कि फ् य ू ज का ऑपरे ट िं ग समय 0.5 से क ं ड से कम है । स्...
  • Page 131 HI -त् व रित इं स ् ट ाले श न और स् ट ार् ट -अप गाइड 131 ड् र ाइव इं स ् ट ाल करे ं आप ड् र ाइव इं स ् ट ाल कर सकते है ं •...
  • Page 132 132 HI -त् व रित इं स ् ट ाले श न और स् ट ार् ट -अप गाइड • सु न िश् च ित करे ं कि दीवार और फिक् स िं ग उपकरण वज़ न उठा सकते हों । नीचे टे ब ल मे ं डे ट ा दे...
  • Page 133 HI -त् व रित इं स ् ट ाले श न और स् ट ार् ट -अप गाइड 133 फ् र ै म R0 मे ं माउं ट करने वाले पे ं च का नीचे उदाहरण दे ख े ं । 6.
  • Page 134 Use a measuring voltage of 1000 V DC. The insulation resistance of an ABB motor must be more than 100 Mohm (reference value at 25 C [77°F]). For the insulation resistance of other motors, refer to the manufacturer’s instructions.
  • Page 135 HI -त् व रित इं स ् ट ाले श न और स् ट ार् ट -अप गाइड 135 पावर के ब लों को कने क ् ट करना ■ कने क ् श न आरे ख विकल् प ों के लिए, हार् ड वे य र मै न ् य ु अ ल दे ख े ं । एक...
  • Page 136 136 HI -त् व रित इं स ् ट ाले श न और स् ट ार् ट -अप गाइड ■ कने क ् श न प् र क् र िया: फ् र े म R0…R2 If the drive is connected on an IT (ungrounded) system, make sure that the EMC filter and Varistor (VAR) is disconnected.
  • Page 137 HI -त् व रित इं स ् ट ाले श न और स् ट ार् ट -अप गाइड 137 3. मोटर के ब ल को निम् न ु स ार कने क ् ट करे ं : • Ground the shield 360° by tightening the clamp of the power cable grounding shelf onto the stripped part of the cable (3a).
  • Page 138 138 HI -त् व रित इं स ् ट ाले श न और स् ट ार् ट -अप गाइड इनपु ट पावर के ब ल 4. चित् र मे ं दिखाए अनु स ार के ब ल के सिरों को तै य ार करे ं । टिप्...
  • Page 139 HI -त् व रित इं स ् ट ाले श न और स् ट ार् ट -अप गाइड 139 9. पे ं च ों को नीचे दिए गए टॉर् क पर कसे ं । फ् र े म आकार R0…R1 N·m lbf·ft N·m...
  • Page 140 140 HI -त् व रित इं स ् ट ाले श न और स् ट ार् ट -अप गाइड ■ कने क ् श न प् र क् र िया, फ् र े म R3 ... R4 If the drive is connected on an IT (ungrounded) system, make sure you have disconnected the EMC filter and Varistor (VAR).
  • Page 141 HI -त् व रित इं स ् ट ाले श न और स् ट ार् ट -अप गाइड 141 3. मोटर के ब ल को निम् न ु स ार कने क ् ट करे ं : If the power cable is temporarily removed from the grounding shelf, connect the motor and input power cables except the 360°...
  • Page 142 142 HI -त् व रित इं स ् ट ाले श न और स् ट ार् ट -अप गाइड इनपु ट पावर के ब ल 4. चित् र मे ं दिखाए अनु स ार के ब ल के सिरों को तै य ार करे ं । टिप्...
  • Page 143 HI -त् व रित इं स ् ट ाले श न और स् ट ार् ट -अप गाइड 143 9. R3 के लिए, कं ड क् ट रों को R+ और R- टर् म िनलों (7c) से कने क ् ट करे ं । 10.
  • Page 144 144 HI -त् व रित इं स ् ट ाले श न और स् ट ार् ट -अप गाइड 12. Ground the motor cable shield at the motor end. For minimum radio frequency interference, ground the motor cable shield 360° at the lead-through of the motor terminal box.
  • Page 145 HI -त् व रित इं स ् ट ाले श न और स् ट ार् ट -अप गाइड 145 ■ कने क ् श न प् र क् र िया, फ् र े म R5…R8 86 Electrical installation If the drive will be connected on an IT (ungrounded) system, make sure you have 86 Electrical installation disconnected the EMC filter and Varistor (VAR).
  • Page 146 146 HI -त् व रित इं स ् ट ाले श न और स् ट ार् ट -अप गाइड 7. Prepare the ends of the input power cable and motor cable as illustrated in the figure. If you use aluminum cables, put grease on the peeled aluminum cable before connecting it to the drive.
  • Page 147 HI -त् व रित इं स ् ट ाले श न और स् ट ार् ट -अप गाइड 147 M5×25/35 फ् र े म आकार L1, L2, L3, T1/U, T2/V, T3/W N·m lbf·ft N·m lbf·ft N·m lbf·ft 22.1 29.5 29.5 T1/U, T2/V और...
  • Page 148 148 HI -त् व रित इं स ् ट ाले श न और स् ट ार् ट -अप गाइड 11. के व ल फ़् र े म R8: यदि आप समानां त र के ब ल इं स ् ट ाल करते है ं , तो समानां त र पॉवर के ब लों के लिए दू स रा ग्...
  • Page 149 फर् म वे य र मै न ु अ ल मे ं वर् ण ित के ब ल् स को कने क ् ट करे ं । ABB मानक मै क ् र ो के नीचे डिफ़ ॉ ल् ट...
  • Page 150 150 HI -त् व रित इं स ् ट ाले श न और स् ट ार् ट -अप गाइड डिफ़ ॉ ल् ट I/O कने क ् श न (ABB स् ट ॅ ं ड र् ड मै क ् र ो) ■...
  • Page 151 Fieldbus module (in frames R0...R2 frames, fieldbus module can be used with BIO-01 also) समर् थ ित फ़ ी ल् ड बस मॉड् य ू ल के बारे मे ं जानकारी के लिए, ACS560 उत् प ाद कै ट लॉग दे ख े ं ।...
  • Page 152 152 HI -त् व रित इं स ् ट ाले श न और स् ट ार् ट -अप गाइड For more information on optional modules, see hardware manual. ■ हार् ड वे य र का विवरण उत् प ाद अवलोकन The BIO-01 front option module (Option +L515) is an I/O extension module for R0...R2 frames and can also be used with any of the fieldbus optional module.
  • Page 153: Electrical Installation

    2. मौजू द ा RIIO-01 मॉड् य ू ल निकाले ं । निकाल दे न ा, टिप् प णी RIIO-01 मॉड् य ू ल मानक ACS560-01 R0 ... R2 ड् र ाइव मे ं डिफ़ ॉ ल् ट रू प से उपलब् ध है ।...
  • Page 154 154 HI -त् व रित इं स ् ट ाले श न और स् ट ार् ट -अप गाइड 132 Electrical installation c. मॉड् य ू ल को खीं च े ं और इसे हटा दे ं । Installing option modules टिप्...
  • Page 155 HI -त् व रित इं स ् ट ाले श न और स् ट ार् ट -अप गाइड 155 IT (अनग् र ाउं ड ड) और कोने मे ं ग् र ाउं ड ड TN सिस् ट मों की अनु क ू ल ता की जां च करना...
  • Page 156 156 HI -त् व रित इं स ् ट ाले श न और स् ट ार् ट -अप गाइड फ् र े म के EMC फ़ ि ल् ट र Ground- to- सममित आधार पर कोने पर ग् र ाउं ड ड TN IT सिस्...
  • Page 157 HI -त् व रित इं स ् ट ाले श न और स् ट ार् ट -अप गाइड 157 कवरों को पु न र् स ् थ ापित करना ■ कवरों को पु न र् स ् थ ापित करना, फ् र े म आकार R0…R2 1.
  • Page 158 158 HI -त् व रित इं स ् ट ाले श न और स् ट ार् ट -अप गाइड ■ साइड प् ल े ट ् स और कवरों को पु न र् स ् थ ापित करना, फ् र े म आकार R5…R8 1.
  • Page 159 HI -त् व रित इं स ् ट ाले श न और स् ट ार् ट -अप गाइड 159 यदि के ब ल कॉनड् य ु ट बॉक् स का उपयोग किया जाता है , तो निम् न कार् य करे ं : फ़्...
  • Page 160 160 HI -त् व रित इं स ् ट ाले श न और स् ट ार् ट -अप गाइड शु र ू करे ं और प् र योग मे ं लाएं इस अनु भ ाग मे ं मू ल नियं त ् र ण पै न ल का प् र योग करते हु ए ड् र ाइव इं स ् ट ाल करने और शु र ू करने के बारे मे ं निर् द े श दिए...
  • Page 161 HI -त् व रित इं स ् ट ाले श न और स् ट ार् ट -अप गाइड 161 ■ डिस् प ् ल े नियं त ् र ण पै न ल डिस् प ् ल े निम् न तत् व दिखाता है : नियं...
  • Page 162 162 HI -त् व रित इं स ् ट ाले श न और स् ट ार् ट -अप गाइड ■ मु ख ् य मे न ू Motor data Motor control Connection macro डायग् न ोस् ट िक Energy Efficiency Backup data Parameter settings Complete parameter list...
  • Page 163 HI -त् व रित इं स ् ट ाले श न और स् ट ार् ट -अप गाइड 163 मोटर डे ट ा इस मे न ू मे ं मान मोटर रे ट िं ग प् ल े ट पर आधारित है ं । पै र ामीटर समू ह दे ख े ं 98 उपयोगकर् त ा मोटर पै र ामीटर . टिप्...
  • Page 164 164 HI -त् व रित इं स ् ट ाले श न और स् ट ार् ट -अप गाइड Start mode – Automatic, constant time, Fast Stop mode – Coast, Ramp Acceleration time - Time for speed to change from zero to the speed defined by parameter. Deceleration time - Time for speed to change from the speed defined by parameter to zero.
  • Page 165 Macro - Displays the selected macro name. For example, ABB standard (2-wire). I/O Connections - Displays the selected macro-specific I/O connections. See menu description below. → चु न ा हु आ मै क ् र ो ABB स् ट ै ं ड र् ड (2 -तार) है ।...
  • Page 166 3) ABB स् ट ै ण ् ड र् ड (वे क ् ट र) - मानक मै क ् र ो के समान ले क िन वे क ् ट र नियं त ् र ण का उपयोग करता है...
  • Page 167 HI -त् व रित इं स ् ट ाले श न और स् ट ार् ट -अप गाइड 167 DI - Digital Inputs DI1...DI6 AI - Analog Inputs AI1...AI2 RO - Relay Outputs RO1...RO3 AO1 - Analog Outputs AO1...AO2 AI1 and AI2 values AO1 and AO2 values...
  • Page 168 168 HI -त् व रित इं स ् ट ाले श न और स् ट ार् ट -अप गाइड डायग् न ोस् ट िक सक् र िय फ़ ॉ ल् ट और चे त ावनियाँ और उन् ह े ं कै स े ठीक और रिसे ट किया जाए यह दिखाता है । फ़ ॉ ल् ट और चे त ावनी कोड...
  • Page 169 HI -त् व रित इं स ् ट ाले श न और स् ट ार् ट -अप गाइड 169 बै क अप डे ट ा ड् र ाइव और पै न ल के बीच डे ट ा रिस् ट ोर और बै क अप करे ं । Backup from the drive to the control panel.
  • Page 170 170 HI -त् व रित इं स ् ट ाले श न और स् ट ार् ट -अप गाइड Reference value: Speed (rpm) or frequency (Hz) Rotation direction: Forward or reverse Faults: Active fault code Warnings: Active warning code गति या फ् र िक् व े ं स ी रे फ रे ं स से ट करना विकल्...
  • Page 171 HI -त् व रित इं स ् ट ाले श न और स् ट ार् ट -अप गाइड 171 घू म ने की दिशा को बदलना विकल् प मे न ू मे ं , तीर बटनों का प् र योग करते हु ए घू र ् ण ी दिशा (2) आइटम पर जाएं । मोटर...
  • Page 172 172 HI -त् व रित इं स ् ट ाले श न और स् ट ार् ट -अप गाइड ईन् प ु ट / आउटपु ट और फील् ड बस मॉड् य ू ल की ऑटो कॉन् फ ़ ि गरे श न आप...
  • Page 173 HI -त् व रित इं स ् ट ाले श न और स् ट ार् ट -अप गाइड 173 ड् र ाइव और पै न ल सं च ार विफलता ड् र ाइव सं च ार विफलता के दौरान पै न ल कमां ड के प् र ति उत् त र नहीं दे त ी है । ड्...
  • Page 174 174 HI -त् व रित इं स ् ट ाले श न और स् ट ार् ट -अप गाइड...
  • Page 175 पै र ामीटर सू च ी 175 पै र ामीटर सू च ी सू च ी नाम रे ं ज यू न िट चू क 01 वास् त विक मू ल ् य 01.01 मोटर गति प् र यु क ् त -30000.00…30000.00 01.02 अनु...
  • Page 176 176 पै र ामीटर सू च ी सू च ी नाम रे ं ज यू न िट चू क 01.68 Abs मोटर शाफ् ट पॉवर 0.00 … 32767.00 kW or hp 03 इनपु ट रे फ रे ं स 03.01 पै...
  • Page 177 आश् र य उपयोग किया गया गलती पर -30000.00...30000.00 0.00 05.99 BIO-01 DIP switch status टिप् प णी [ Translation This feature is not missing] available with the standard BIO-01. For information on the availability on new BIO- 01 module, contact ABB sales team.
  • Page 178 178 पै र ामीटर सू च ी सू च ी नाम रे ं ज यू न िट चू क नाम 0 = OFF = DO1 on port S1, 1 = ON = AO1 on port S1 0 = OFF = DI3 on port S2 1 = ON = DO1 on port S2 2...5 आरक्...
  • Page 179 पै र ामीटर सू च ी 179 सू च ी नाम रे ं ज यू न िट चू क 06.16 ड् र ाइव स् ट े ट स शब् द 1 0b0000...0b1111 0b0000 नाम नाम नाम सक् ष म प् र ारं भ किया गया Ext1 सक्...
  • Page 180 180 पै र ामीटर सू च ी सू च ी नाम रे ं ज यू न िट चू क नाम नाम नाम शू न ् य गति 2...6 रिवर् स 8...15 आरक् ष ित फॉरवर् ड किसी स् थ िर गति का...
  • Page 181 पै र ामीटर सू च ी 181 सू च ी नाम रे ं ज यू न िट चू क नाम नाम नाम नाम FLON-01 FCNA-01 CMOD-02 CHDI-01 FDNA-01 CMOD-01 CPTC-01 5…15 आरक् ष ित `0 स् ट ै ं ड र् ड DI, RO 10.01 DI स्...
  • Page 182 182 पै र ामीटर सू च ी सू च ी नाम रे ं ज यू न िट चू क 10.24 RO1 सोर् स 0...2, 4...24, 27...35, 45...48 चलाने के लिए तै य ार[2] सक् र िय नहीं [ 0] सीमा से ऊपर[12] Ext2 सक्...
  • Page 183 पै र ामीटर सू च ी 183 सू च ी नाम रे ं ज यू न िट चू क 12 स् ट ै ण ् ड र् ड AI 12.02 AI फोर् स चयन 0b000...0b1111 0b0000 नाम नाम नाम 2...15 आरक्...
  • Page 184 184 पै र ामीटर सू च ी सू च ी नाम रे ं ज यू न िट चू क 13.11 AO1 वास् त विक मान 0.000 … 22.000 13.12 AO1 सोर् स 0...1, 3...8, 12, 14, 16, 20, 21, आउटपु ट फ् र िक् व े न ् स ी[3] 26...28, 30...32, 37, 38 शू...
  • Page 185 पै र ामीटर सू च ी 185 सू च ी नाम रे ं ज यू न िट चू क 19.11 Ext1/Ext2 चयन 0...8, 19...21, 25...27, 32...34 EXT1[0] EXT1[0] DI2[4] DI6[8] सु प रविज़न 1[25] FBA A कने क ् श न हानि[33] EXT2[1] DI3[5]...
  • Page 186 186 पै र ामीटर सू च ी सू च ी नाम रे ं ज यू न िट चू क 20.07 Ext2 स् ट ार् ट ट् र िगर प् र कार एज[0], ले व ल[1] ले व ल[1] 20.08 1 सोर् स मे ं Ext2 पै...
  • Page 187 पै र ामीटर सू च ी 187 सू च ी नाम रे ं ज यू न िट चू क 21.06 शू न ् य गति सीमा 0…30000 30.00 21.07 शू न ् य गति दे र ी 0…30000 21.08 DC करं ट कं ट ् र ोल 0b0000…0b1111 0b0000 नाम...
  • Page 188 188 पै र ामीटर सू च ी सू च ी नाम रे ं ज यू न िट चू क 22.01 Speed reference unlimited -30000.00...30000.00 0.00 22.11 Ext1 गति रे फ रे ं स 1 0...2, 4, 5, 8, 9, 15...19 AI1 स्...
  • Page 189 पै र ामीटर सू च ी 189 सू च ी नाम रे ं ज यू न िट चू क 22.42 जॉगिं ग 1 रे फ रे ं स -30000.00 … 30000.00 0.00 22.43 जॉगिं ग 2 रे फ रे ं स -30000.00 …...
  • Page 190 190 पै र ामीटर सू च ी सू च ी नाम रे ं ज यू न िट चू क 23.11 रै म ् प से ट चयन 0...7, 20 DI5[6] एक् स े ल रे श न/डिसे ल रै श न समय DI2[3] DI5[6] EFB DCU CW bit 10[20]...
  • Page 191 पै र ामीटर सू च ी 191 सू च ी नाम रे ं ज यू न िट चू क 25.56 टॉर् क एक् स े ल रे श न पू र ित -30000.0 … 30000.0 26 टॉर् क रे फ रे ं स चे न 26.01 TC के...
  • Page 192 192 पै र ामीटर सू च ी सू च ी नाम रे ं ज यू न िट चू क 26.81 रश नियं त ् र ण लाभ 0.0...10000.0 26.82 रश नियं त ् र ण एकीकरण समय 0.0...10.0 28 फ् र िक् व े न ् स ी रे फ रे ं स चे न 28.01 फ्...
  • Page 193 पै र ामीटर सू च ी 193 सू च ी नाम रे ं ज यू न िट चू क 28.28 स् थ िर फ् र िक् व े ं स ी 3 -500.00 … 500.00 15.00 28.29 स् थ िर फ् र िक् व े ं स ी 4 -500.00 …...
  • Page 194 194 पै र ामीटर सू च ी सू च ी नाम रे ं ज यू न िट चू क 30.01 सीमा शब् द 1 0b0000…0b1111 0b0000 नाम नाम नाम टॉर् क सीमा Tlim अधिकतम अधिकतम गति फ् र िक् व े ं स ी रे फ रे ं स सीमा...
  • Page 195 पै र ामीटर सू च ी 195 सू च ी नाम रे ं ज यू न िट चू क 30.21 न् य ू न तम टोक़ 2 स् र ोत न् य ू न तम टार् क 2[16] शू न ् य [0] AI1 स्...
  • Page 196 196 पै र ामीटर सू च ी सू च ी नाम रे ं ज यू न िट चू क 31.10 बाहरी इवे ं ट 5 प् र कार फॉल् ट [0], चे त ावनी[1] फॉल् ट [0] 31.11 फॉल् ट रिसे ट चयन उपयोग...
  • Page 197 पै र ामीटर सू च ी 197 सू च ी नाम रे ं ज यू न िट चू क 31.36 Aux fan fault function Fault[0], Warning[1], No चे त ावनी[1] action[2] टिप् प णी This parameter is only applicable for frames R3 or larger.
  • Page 198 198 पै र ामीटर सू च ी सू च ी नाम रे ं ज यू न िट चू क 32.15 सु प रविज़न 2 फं क ् श न पै र ामीटर दे ख े ं 32.05 सु प रविज़न 1 अक्...
  • Page 199 पै र ामीटर सू च ी 199 सू च ी नाम रे ं ज यू न िट चू क 32.50 सु प रविज़न 5 उच् च -21474836.00… 0.00 21474836.00 32.51 सु प रविज़न 5 हिस् ट ै र िसीस 0.00...100000.00 0.00 32.55 सु...
  • Page 200 200 पै र ामीटर सू च ी सू च ी नाम रे ं ज यू न िट चू क नाम नाम नाम नाम सोमवार शु क ् र वार मौसम 2 छु ट ् ट ियाँ मं ग लवार शनिवार मौसम...
  • Page 201 पै र ामीटर सू च ी 201 सू च ी नाम रे ं ज यू न िट चू क 34.41 टाइमर 11 कॉन् फ़ िगरे श न पै र ामीटर दे ख े ं 34.11 टाइमर 1 0b0111 कॉन् फ़ िगरे श न 34.42 टाइमर...
  • Page 202 202 पै र ामीटर सू च ी सू च ी नाम रे ं ज यू न िट चू क नाम नाम नाम नाम नाम टाइमर 1 टाइमर 4 टाइमर 7 टाइमर 10 12...15 आरक् ष ित Timer 2 टाइमर 5 टाइमर...
  • Page 203 पै र ामीटर सू च ी 203 सू च ी नाम रे ं ज यू न िट चू क 35.22 तापमान 2 फॉल् ट सीमा -60…5000 °C °C 130 °C 35.23 तापमान 2 चे त ावनी सीमा -60…5000 °C °C 110 °C 35.24 तापमान...
  • Page 204 204 पै र ामीटर सू च ी सू च ी नाम रे ं ज यू न िट चू क चयनित नहीं [ 0] मोटर करं ट %[2] ड् र ाइव नॉमिनल आउटपु ट अन् य ... पॉवर %[4] मोटर गति %[1] मोटर...
  • Page 205 पै र ामीटर सू च ी 205 सू च ी नाम रे ं ज यू न िट चू क नाम नाम नाम नाम नाम ट् र ै क िं ग डे ड बै ं ड आतं र िक सक् र िय स्...
  • Page 206 206 पै र ामीटर सू च ी सू च ी नाम रे ं ज यू न िट चू क चयनित नहीं [ 0] DI2[3] DI5[6] समयबद् ध फं क ् श न सु प रविज़न 2[22] 2[19] चयनित[1] DI3[4] DI6[7] समयबद्...
  • Page 207 पै र ामीटर सू च ी 207 सू च ी नाम रे ं ज यू न िट चू क 40.52 Set 1 trim selection टार् क [1], गति[2], फ् र ीक् व े ं स ी [3] गति[2] 40.53 Set 1 trimmed ref pointer 0...4 चयनित...
  • Page 208 208 पै र ामीटर सू च ी सू च ी नाम रे ं ज यू न िट चू क 40.92 से ट प् व ॉइं ट डे ट ा सं ग ् र ह -327.68…327.68 0.00 40.96 प् र ोसे स PID आउट% -100.00...100.00 0.00 40.97...
  • Page 209 पै र ामीटर सू च ी 209 सू च ी नाम रे ं ज यू न िट चू क 41.40 से ट 1 डे ड बै ं ड दे र ी 0.0 … 3600.0 41.43 से ट 2 स् ल ीप ले व ल 0.0 …...
  • Page 210 210 पै र ामीटर सू च ी सू च ी नाम रे ं ज यू न िट चू क अक् ष म[0] थर् म ल मॉडल द् व ारा थर् म ल मॉडल सक् ष म[2] अधिक वोल् ट े ज से सु र क् ष ा[3] सक्...
  • Page 211 पै र ामीटर सू च ी 211 सू च ी नाम रे ं ज यू न िट चू क 45.21 ऊर् ज ा गणना रिसे ट पू र ा किया[0], रिसे ट करे ं [ 1] पू र ा किया[0] 45.24 प्...
  • Page 212 212 पै र ामीटर सू च ी सू च ी नाम रे ं ज यू न िट चू क 47.11 डे ट ा सं ग ् र ह 1 int32 -2147483648 … 2147483647 47.12 डे ट ा सं ग ् र ह 2 int32 -2147483648 …...
  • Page 213 पै र ामीटर सू च ी 213 सू च ी नाम रे ं ज यू न िट चू क कोई कार् य वाही फॉल् ट [1] अं त िम गति[2] गति रे फ रे ं स हमे श ा फॉल् ट [4] चे...
  • Page 214 214 पै र ामीटर सू च ी सू च ी नाम रे ं ज यू न िट चू क कॉन् फ़ िगर नहीं किया गया[0] समय समाप् त [2] ऑफ़-लाइन[4] रिसे ट करे ं [ 6] आरं भ किया जा रहा है [ 1] कॉन्...
  • Page 215 EFB स् ट े ट स शब् द 0000h…FFFFh 58.25 कं ट ् र ोल प् र ोफाइल ABB ड् र ाइव् स [0], DCU ABB ड् र ाइव् स [0] प् र ोफाइल[5] 58.26 EFB रे फ रे ं स 1 टाइप...
  • Page 216 216 पै र ामीटर सू च ी सू च ी नाम रे ं ज यू न िट चू क कोई नहीं [ 0] SW 16बिट[4] रे फ रे ं स 1 32बिट[12] Act2 32बिट[16] AO1 डे ट ा स् ट ोरे ज [32] CW 16बिट[1] Act1 16बिट[5] रे...
  • Page 217 पै र ामीटर सू च ी 217 सू च ी नाम रे ं ज यू न िट चू क फॉरवर् ड [0] DI2[3] DI5[6] -DI2[9] -DI5[12] रिवर् स [1] DI3[4] DI6[7] -DI3[10] -DI6[13] DI1[2] DI4[5] -DI1[8] -DI4[11] अन् य ... 70.06 फ्...
  • Page 218 218 पै र ामीटर सू च ी सू च ी नाम रे ं ज यू न िट चू क 71.31 डे व िएशन इन् व र् ज न पै र ामीटर दे ख े ं 40.31 से ट 1 उल् ट ा नहीं किया (रे फ रे न ् स डे...
  • Page 219 पै र ामीटर सू च ी 219 सू च ी नाम रे ं ज यू न िट चू क 76.02 PFC सिस् ट म स् ट े ट स 0...9, 100...103, 200...202, PFC अक् ष म[0] 300...302, 400, 500, 600, 700, 800, 801, PFC अक्...
  • Page 220 220 पै र ामीटर सू च ी सू च ी नाम रे ं ज यू न िट चू क 76.59 PFC कॉं ट ् र े क ् ट र दे र ी 0.20…600.00 0.50 76.60 PFC रै म ् प एक् स े ल रे श न समय 0.00…1800.00 1.00 76.61...
  • Page 221 24V[1] 95.15 विशे ष HW से ट िं ग 0b0000…0b1111 0b0000 नाम नाम नाम आरक् ष ित ABB साइन 2...15 आरक् ष ित फिल् ट र 95.20 हार् ड वे य र विकल् प शब् द 1 0b0000…0b1111 0b0000 नाम...
  • Page 222 3-wire[11] PFC[16] प् ल ास् ट िक उभार[20] मोटर पोटे ं श ियोमीटर[13] ABB मानक (वे क ् ट र)[17] Torque control[28] 96.05 मै क ् र ो सक् र िय पै र ामीटर दे ख े ं 96.04 मै क ् र ो चयन...
  • Page 223 10000000…99999999 96.102 यू ज़ र लॉक व् य वहारिकता 0000h…FFFFh 0000h ABB एक् स े स स् त र अक् ष म Reserved[3...5] आरक् ष ित[8...10] OEM एक् स े स स् त र 3 करे ं [ 0] अक् ष म करे ं [ 13] पै...
  • Page 224 224 पै र ामीटर सू च ी सू च ी नाम रे ं ज यू न िट चू क 97.13 IR पू र ् त ि 0.00 … 50.00 3.50 97.20 U/F अनु प ात सीधा[0], वर् ग ाकार[20] सीधा[0] 97.48 UDC stabilizer अक्...
  • Page 225 ड् र ाइव प् र कार Nominal अधि. आउटपु ट रे ट िं ग ् स फ् र े म ACS560 करं ट आकार सां क े त िक प् र योग लाइट ओवरलोड उपयोग है व ी-ड् य ू ट ी प् र योग...
  • Page 226 न् य ू न तम शॉर् ट ACS560 सर् क िट रे ट ड करं ट I रे ट ड वोल् ट े ज ABB निर् ध ारण IEC 60269 वर् त मान प् र कार आकार 3 फे ज ़ U = 400 V (380...480 V)
  • Page 227 (IEC 60269) न् य ू न तम शॉर् ट ACS560 सर् क िट रे ट ड करं ट I रे ट ड वोल् ट े ज ABB निर् ध ारण IEC 60269 वर् त मान प् र कार आकार 12A6-4 20.2...
  • Page 228 228 तकनीकी डे ट ा ड् र ाइव प् र कार इनपु ट करं ट gG (IEC 60269) न् य ू न तम शॉर् ट ACS560- सर् क िट रे ट ड करं ट I रे ट ड वोल् ट े ज IEC 60269 वर्...
  • Page 229 आदर् श पावर के ब ल के आकार ड् र ाइव प् र कार फ् र े म आकार ACS560 Cu के ब ल प् र कार Cu के ब ल प् र कार AI के ब ल प् र कार...
  • Page 230 230 तकनीकी डे ट ा Frame आयाम और वजन IP20 वजन 28.3 42.4 Standard frames...
  • Page 231 तकनीकी डे ट ा 231 चिह् न IP20 अगले हिस् स े की ऊँ च ाई पिछले हिस् स े की ऊँ च ाई (के ब ल को जोड़ न े वाले बॉक् स के बिना) चौड़ ा ई गहराई ड्...
  • Page 232 232 तकनीकी डे ट ा लागू मानक ड् र ाइव निम् न लिखित मानकों का पालन करती है । यू र ोपीय कम वोल् ट े ज निदे श कों के साथ अनु प ालन की मानक EN 61800-5-1 के अनु स ार पु ष ् ट ि की जाती है । EN 60204-1:2006 + AC:2010 मशीन...
  • Page 233 तकनीकी डे ट ा 233 ■ यू र ोपीय कम वोल् ट े ज निदे श का अनु प ालन The compliance with the European Low Voltage Directive has been verified according to standard EN 61800-5-1:2007. The declaration of conformity (3AXD10000549832) is available on the Internet.
  • Page 234 234 तकनीकी डे ट ा ■ यू र ोपीय EMC निदे श का अनु प ालन The EMC Directive defines the requirements for immunity and emissions of electrical equipment used within the European Union. The EMC product standard (EN 61800- 3:2004 + A1:2012) covers requirements stated for drives.
  • Page 235 यू र ोपीय मशीनरी निदे श 2006/42/EC द् व ितीय सं स ् क रण - जू न 2010 का अनु प ालन EU Declaration of Conformity Machinery Directive 2006/42/EC Manufacturer: ABB India Limited Address: Plot No 5 &6 , 2...
  • Page 236 AR Madhusudhan Laxmikantha shenoy Vice President, MODP Manager , Prodcut Engineering ABB India Limited ABB India Limited 3AXD10000549832 Rev. 3 IMS template code: 3AFE011906, Rev. C ड् र ाइव एक मशीनरी घटक है जिसे मशीनरी निर् द े श क 2006/42/EC द् व ितीय सं स ् क रण - जू न 2010 के अप् ल िके श न...
  • Page 237 डायग् न ोस् ट िक 237 डायग् न ोस् ट िक चे त ावनी सं द े श कोड (hex) चे त ावनी / ऑक् स कोड कारण क् य ा करे ं (ऑक् स कोड के व ल सहायक नियं त ् र ण कक् ष और...
  • Page 238 मे ज़ रमे ं ट सर् क िट तापमान ड् र ाइव आतं र िक तापमान माप मे ं फॉल् ट । अपने स् थ ानीय ABB प् र तिनिधि से सं प र् क करे ं । A5EB PU बोर् ड पॉवरफे ल...
  • Page 239 A684 पावर असफल बचत पावर असफल बचत चे त ावनी अपने स् थ ानीय ABB प् र तिनिधि से सं प र् क करे ं । A6A4 मोटर नॉमिनल मान मोटर मानदं ड गलत ढं ग से स् थ ापित है ं ।...
  • Page 240 If no issue was detected and drive output was actually connected to motor, contact ABB. A791 ब् र े क रे ज़ िस् ट े ं स ब् र े क रज़ ि स् ट र फॉल् ट ।...
  • Page 241 डायग् न ोस् ट िक 241 कोड (hex) चे त ावनी / ऑक् स कोड कारण क् य ा करे ं (ऑक् स कोड के व ल सहायक नियं त ् र ण कक् ष और ड् र ाइव सं ग ीतकार पर दिखाई...
  • Page 242 242 डायग् न ोस् ट िक कोड (hex) चे त ावनी / ऑक् स कोड कारण क् य ा करे ं (ऑक् स कोड के व ल सहायक नियं त ् र ण कक् ष और ड् र ाइव सं ग ीतकार पर दिखाई...
  • Page 243 डायग् न ोस् ट िक 243 कोड (hex) चे त ावनी / ऑक् स कोड कारण क् य ा करे ं (ऑक् स कोड के व ल सहायक नियं त ् र ण कक् ष और ड् र ाइव सं ग ीतकार पर दिखाई...
  • Page 244 मोटर के ब ल् स और मोटर के इन् स ु ल े श न प् र तिरोध को मापे ं । अपने स् थ ानीय ABB प् र तिनिधि से सं प र् क करे ं । 3130 इनपु ट फे ज़ हानि...
  • Page 245 डायग् न ोस् ट िक 245 कोड (hex) Fault / Aux. code कारण क् य ा करे ं aux code visible only on assistant control panel and drive composer)) 3181 वायरिं ग या अर् थ फॉल् ट गलत इनपु ट पॉवर और मोटर के ब ल इनपु...
  • Page 246 STO हार् ड वे य र डायग् न ोस् ट िक से हार् ड वे य र बदलने के लिए ABB से सं प र् क करे ं । हार् ड वे य र विफलता का पता चला है ।...
  • Page 247 आं त रिक गलती नियं त ् र ण यू न िट रीबू ट करे ं । यदि समस् य ा बनी रहती है , तो ABB प् र तिनिधि से सं प र् क करे ं । 64A3 एप् ल िके श न लोड हो रही...
  • Page 248 EFB कॉन् फ़ िगरे श न एम् ब े ड े ड फील् ड बस (EFB) फार् म वे य र दोबारा लोड करे ं या यू न िट बदले ं । ABB से फ़ाइल कॉन् फ ़ ि गरे श न फ़ ा इल को पढ़ ा नहीं जा...
  • Page 249 उत् त े ज ना वर् त मान उत् त े ज ना वर् त मान प् र तिक् र िया कम या अपने स् थ ानीय ABB प् र तिनिधि से सं प र् क करे ं । गायब है...
  • Page 250 250 डायग् न ोस् ट िक कोड (hex) Fault / Aux. code कारण क् य ा करे ं aux code visible only on assistant control panel and drive composer)) 00FA मोटर न् य ू न तम उच् च तम आवृ त ् त ि से ट न्...
  • Page 251 डायग् न ोस् ट िक 251 कोड (hex) Fault / Aux. code कारण क् य ा करे ं aux code visible only on assistant control panel and drive composer)) 1 - AI1कम न् य ू न तम 3 - AI2कम न् य ू न तम 2 - AI1अधिक...
  • Page 252 252 डायग् न ोस् ट िक कोड (hex) Fault / Aux. code कारण क् य ा करे ं aux code visible only on assistant control panel and drive composer)) 1 - अधिकतम करं ट सीमा बहु त कम है (के व ल असिं क ् र ोनस मोटर) ID चालू के दौरान गति शू न ् य तक...
  • Page 253: Further Information

    Product and service inquiries Address any inquiries about the product to your local ABB representative, quoting the type designation and serial number of the unit in question. A listing of ABB sales, support and service contacts can be found by navigating to www.abb.com/searchchannels.
  • Page 254 3AXD50000042620H © 2020 ABB Oy. All rights reserved. Specifications subject to change without notice.

Table of Contents