ABB ACS510-01 User Manual page 128

Low voltage ac drives
Table of Contents

Advertisement

128
– Drive waits for PFC Start Delay(parameter 8122). Modulation is not allowed
because drive has to wait that all contactor are stabilized.
– Modulation is allowed. Modulation starts from zero speed. After F
Start Frequency 1, Aux. Mot. Start Delay starts (parameter 8115).
– When Aux. Mot. Start Delay elapses then drive coasts to stop and RO1 is
opened.
– Drive waits for PFC Start Delay (parameter 8122). Meaning of this delay it to
wait contactors to stabilize. If there is some oscillation in Motor 1 contactors
when closing RO2, then contactors might go to wrong state.
– Drive close RO2. This is new plae for Speed Regulated Motor. Modulation is
not allow yet.
– Drive waits for PFC Start Delay (parameter 8122). Modulation is not allowed
because the drive has to wait that all contactors are stabilized.
– Drive close RO1. Motor in RO1 is connected directly to the network(constant
speed) and modulation is allowed. Drive start accelerating from zero in RO2.
• Stoping motors goes like in standard PFC. See the figure.
8109 START LOW FREQ 1
Start-Up
Supplied from China by: Guangzhou Tofee Electro Mechanical Equipment Co., Ltd
Email: info@tofee.com.cn
Motor in RO1 is Speed Req Motor
1.
FOut
2.
Start
RO1 /Motor1
RO2 /Motor2
8122 PFC START DLY
Speed Req Motor in RO2
FOut
Start
Motor in RO2 is
RO2 /Motor1
Speed Req Motor
RO1 /Motor2
Motor in RO1 is
Aux Motor
8109 START START FREQ 1
4.
3.
Motor in RO2 is Speed Req Motor
6.
Motor in RO1 is Aux Motor
5.
7.
8.
8122 PFC START DLY
8122 PFC START DLY
ACS510 User's Manual
rises over
out