ABB ACS510-01 User Manual page 137

Low voltage ac drives
Table of Contents

Advertisement

ACS510 User's Manual
Code Description
2 =
2 – Enables the Interlock function, and assigns a digital input (starting with
DI
PFC relay. These assignments are defined in the following table and depend on:
• The number of PFC relays (number of parameters 1401...1403 and 1410...1412) with value = 31
• The Autochange function status (disabled if 8118
No. PFC
Autochange Disabled
Relays
0
1: Free
DI
2: Speed Reg Motor
DI
3...
6: Free
DI
DI
1
1: Free
DI
2: Speed Reg Motor
DI
3: First PFC Relay
DI
4...
6: Free
DI
DI
2
1: Free
DI
2: Speed Reg Motor
DI
3: First PFC Relay
DI
4: Second PFC Relay
DI
5...
6: Free
DI
DI
3
1: Free
DI
2: Speed Reg Motor
DI
3: First PFC Relay
DI
4: Second PFC Relay
DI
5: Third PFC Relay
DI
6: Free
DI
4
1: Free
DI
2: Speed Reg Motor
DI
3: First PFC Relay
DI
4: Second PFC Relay
DI
5: Third PFC Relay
DI
6: Fourth PFC Relay
DI
5
Not allowed
6
Not allowed
Supplied from China by: Guangzhou Tofee Electro Mechanical Equipment Co., Ltd
Email: info@tofee.com.cn
Autochange Enabled
(P 8118)
Not allowed
1: Free
DI
2: First PFC Relay
DI
3...
6: Free
DI
DI
1: Free
DI
2: First PFC Relay
DI
3: Second PFC Relay
DI
4...
6: Free
DI
DI
1: Free
DI
2: First PFC Relay
DI
3: Second PFC Relay
DI
4: Third PFC Relay
DI
5...
6: Free
DI
DI
1: Free
DI
2: First PFC Relay
DI
3: Second PFC Relay
DI
4: Third PFC Relay
DI
5: Fourth PFC Relay
DI
6: Free
DI
1: Free
DI
2: First PFC Relay
DI
3: Second PFC Relay
DI
4: Third PFC Relay
DI
5: Fourth PFC Relay
DI
6: Fifth PFC Relay
DI
Not allowed
= 0, and otherwise enabled).
AUTOCHNG INTERV
(P 8118)
2) to the interlock signal for each
DI
)
PFC
Start-Up
137

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents