Commissioning the override mode:
1. Enter the parameters in all groups as needed, except group 17.
2. Select the digital input that will activate override mode P1701.
3. Enter the frequency reference for override mode, P1702.
4. Enter the pass code P1704 (358).
5. Enable the override mode P1705.
Changing the override parameters:
1. If override mode is already enabled, disable it:
• Enter the pass code P1704.
• Disable the override mode P1705.
2. If needed, load the override parameter set P9902.
3. Change the parameters as needed, except group 17.
4. Change the parameters in group 17 as needed:
• Digital input for override mode P1701.
• Frequency reference P1702.
5. Enter the pass code P1704.
6. Enable the override mode P1705. The drive replaces the override parameter set with
new values of all parameters.
Code Description
1701 OVERRIDE SEL
Selects the source of the override activation signal.
0 = NOT SEL - Override activation signal not selected.
1 = DI1 - Defines digital input DI1 as the override activation signal.
• This digital input must be activated for override activation signal.
2...6 = DI2...DI6 - Defines digital input DI2...DI6 as the override activation signal.
• See DI1 above.
(-1) = DI1(INV) - Defines an inverted digital input DI1 as the override activation signal.
(-2)...(-6) = DI2 (INV)...DI6(INV) - Defines an inverted digital input DI2...DI6 as the override activation
signal.
• See DI1 (INV) above.
1702 OVERRIDE FREQ
Defines a preset frequency for the override.
Start-Up
Supplied from China by: Guangzhou Tofee Electro Mechanical Equipment Co., Ltd
Email: info@tofee.com.cn
1003
PAR AI SCALE
1004
PAR AO SCALE
1006
PAR EXTROMISSING
1007
PAR FBUSMISSING
ACS510 User's Manual