ABB ACS510-01 User Manual page 43

Low voltage ac drives
Table of Contents

Advertisement

ACS510 User's Manual
Application Macro: ABB Standard (Default)
This macro provides a general purpose, 2-wire I/O configuration, with three (3)
constant speeds. This is the default macro. Parameter values are the default values
defined in the "Complete Parameter List for ACS510" on page 52.
Connection example:
X1
• Analog reference (AI1)
• Start, stop and direction (DI1,2)
• Constant speed selection (DI3,4)
• Ramp pair (1 of 2) selection (DI5)
Supplied from China by: Guangzhou Tofee Electro Mechanical Equipment Co., Ltd
Email: info@tofee.com.cn
1
SCR
Signal cable shield (screen)
2
AI1
External frequency reference 1: 0
3
AGND
Analog input circuit common
4
10 V
Reference voltage 10 VDC
5
AI2
Not used
6
AGND
Analog input circuit common
7
AO1
Output frequency: 0
8
AO2
Output current: 0
9
AGND
Analog output circuit common
Auxiliary voltage output +24 VDC
10 24 V
Auxiliary voltage output common
11 GND
Digital input common for all
12 DCOM
Start/Stop: Activate to start
13 DI1
Fwd/Rev: Activate to reverse rotation direction
14 DI2
Constant speed selection
15 DI3
Constant speed selection
16 DI4
Ramp pair selection: Activate to select 2nd acc/dec ramp pair
17 DI5
Not used
18 DI6
19 RO1C
Relay output 1, programmable
Default operation:
20 RO1A
Ready =>19 connected to 21
21 RO1B
22 RO2C
Relay output 2, programmable
Default operation:
23 RO2A
Running =>22 connected to 24
24 RO2B
25 RO3C
Relay output 3, programmable
26 RO3A
Default operation:
Fault (-1) =>25 connected to 27
27 RO3B
(Fault => 25 connected to 26)
Input signals
• Analog output AO1: Frequency
• Analog output AO2: Current
• Relay output 1: Ready
• Relay output 2: Running
• Relay output 3: Fault (-1)
...
10 V
...
20 mA
...
20 mA
1
1
Note 1. Code:
0 = open, 1 = connected
DI3 DI4
0
0
1
0
0
1
1
1
Output signals
43
Output
Reference through AI1
1 (1202)
CONSTANT SPEED
2 (1203)
CONSTANT SPEED
3 (1204)
CONSTANT SPEED
Jumper Setting
J1
...
AI1: 0
10 V
...
AI2: 0(4)
20 mA
Start-Up

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents