Fault
Code
35
36
37
38
101...
199
201...
299
Faults that indicate conflicts in the parameter settings are listed below.
Fault
Code
1000
1001
1003
1004
1005
Diagnostics
Supplied from China by: Guangzhou Tofee Electro Mechanical Equipment Co., Ltd
Email: info@tofee.com.cn
Fault Name In
Panel
Possible power wiring error detected. When the drive is not running it
OUTPUT WIRING
monitors for an improper connection between the drive input power and the
drive output. Check for and correct:
• Proper input wiring – line voltage is NOT connected to drive output.
• The fault can be erroneously declared if the input power is a delta
grounded system and motor cable capacitance is large. This fault can be
disabled using parameter 3023
The drive cannot use the software.
INCOMPATIBLE
SW
• Internal Fault.
• The loaded software is not compatible with the drive.
• Call support representative.
Drive control board is overheated. The fault trip limit is 88 °C. Check for and
CB OVERTEMP
correct:
• Excessive ambient temperature.
• Fan failure.
• Obstructions in the air flow.
Not for drives with an OMIO control board.
Condition defined by parameter 3701
USER LOAD
longer than the time defined by 3703
CURVE
Error internal to the drive. Contact your local ABB representative and report
SYSTEM ERROR
the error number.
Error in the system. Contact your local ABB representative and report the
SYSTEM ERROR
error number.
Fault Name In
Panel
Parameter values are inconsistent. Check for any of the following:
PAR HZRPM
• 2007
MINIMUM FREQ
• 2007
MINIMUM FREQ
(> 50)
• 2008
MAXIMUM FREQ
(> 50)
Parameter values are inconsistent. Check for the following:
PAR PFC REF
NEG
• 2007
MINIMUM FREQ
Parameter values are inconsistent. Check for any of the following:
PAR AI SCALE
• 1301
1
AI
• 1304
2
AI
Parameter values are inconsistent. Check for any of the following:
PAR AO SCALE
• 1504
AO
1510
AO
2
Parameter values for power control are inconsistent: Improper motor
PAR PCU
nominal kVA or motor nominal power. Check for the following:
• 1.1 < (9906
• where: P
or P
= 746 * 9909
N
Description and Recommended Corrective Action
WIRING FAULT
USER LOAD C MODE
USER LOAD C TIME
Description and Recommended Corrective Action
> 2008
MAXIMUM FREQ
/ 9907
MOTOR NOM FREQ
/ 9907
MOTOR NOM FREQ
is negative, when 8123
> 1302
1
.
MIN
AI
MAX
> 1305
2
.
MIN
AI
MAX
1
> 1505
1
.
MIN
AO
MAX
2
> 1511
2
.
MIN
AO
MAX
* 9905
MOTOR NOM CURR
= 1000 * 9909
MOTOR NOM POWER
N
MOTOR NOM POWER
ACS510 User's Manual
.
has been valid
.
.
is outside proper range
is outside proper range
is active.
PFC ENABLE
* 1.73 / P
MOTOR NOM VOLT
N
(if units are kW)
(if units are HP, e.g. in US)
) < 3.0