168
DCU Profile
The following tables describe the
Bit
0
READY
1
ENABLED
2
STARTED
3
RUNNING
4
ZERO_SPEED
5
ACCELERATE
6
DECELERATE
7
AT_SETPOINT
8
LIMIT
9
SUPERVISION
10
REV_REF
11
REV_ACT
12
PANEL_LOCAL
13
FIELDBUS_LOCAL 1
14
EXT2_ACT
15
FAULT
Embedded Fieldbus
Supplied from China by: Guangzhou Tofee Electro Mechanical Equipment Co., Ltd
Email: info@tofee.com.cn
STATUS WORD
DCU Profile
STATUS WORD
Name
Value
1
Drive is ready to receive start command.
0
Drive is not ready.
1
External run enable signal received.
0
No external run enable signal received.
1
Drive has received start command.
0
Drive has not received start command.
1
Drive is modulating.
0
Drive is not modulating.
1
Drive is at zero speed.
0
Drive has not reached zero speed.
1
Drive is accelerating.
0
Drive is not accelerating.
1
Drive is decelerating.
0
Drive is not decelerating.
1
Drive is at setpoint.
0
Drive has not reached setpoint.
1
Operation is limited by Group 20 settings.
0
Operation is within Group 20 settings.
1
A supervised parameter (Group 32) is outside its limits.
0
All supervised parameters are within limits.
1
Drive reference is in reverse direction.
0
Drive reference is in forward direction.
1
Drive is running in reverse direction.
0
Drive is running in forward direction.
1
Control is in control panel (or PC tool) local mode.
0
Control is not in control panel local mode.
Control is in fieldbus local mode (steals control panel local).
0
Control is not in fieldbus local mode.
1
Control is in EXT2 mode.
0
Control is in EXT1 mode.
1
Drive is in a fault state.
0
Drive is not in a fault state.
ACS510 User's Manual
content for the DCU profile.
(See Parameter 0303)
Status