ACS510 User's Manual
Fault
Code
1006
1007
1008
1009
1011
1012
1013
1014
1015
1016
Fault Resetting
The ACS510 can be configured to automatically reset certain faults. Refer to
parameter Group 31: Automatic Reset.
Warning! If an external source for start command is selected and it is active, the
ACS510 may start immediately after fault reset.
Flashing Red LED
To reset the drive for faults indicated by a flashing red LED:
• Turn the power off for 5 minutes.
Red LED
To reset the drive for faults indicated by a red LED (on, not flashing), correct the
problem and do one of the following:
• From the control panel: Press RESET
• Turn the power off for 5 minutes.
Supplied from China by: Guangzhou Tofee Electro Mechanical Equipment Co., Ltd
Email: info@tofee.com.cn
Fault Name In
Panel
Parameter values are inconsistent. Check for the following:
PAR EXT RO
• Extension relay module not connected and
• 1410...1412
Parameter values are inconsistent. Check for and correct:
PAR FIELDBUS
MISSING
• A parameter is set for fieldbus control (e.g. 1001
(
)), but 9802
COMM
REVERSED
1
Parameter values for power control are inconsistent: Improper motor
PAR PCU
nominal frequency or speed. Check for both of the following:
• 1 < (60 * 9907
• 0.8 < 9908
(120 * 9907
See Parameter Group 17.
PAR OVERRIDE
1
PAR PFC IO
IO configuration is not complete – not enough relays are parameterized to
PFC. Or, a conflict exists between Group 14, parameter 8117,
, and parameter 8118,
MOT
2
PAR PFC IO
IO configuration is not complete – the actual number of PFC motors
(parameter 8127,
and parameter 8118
3
PAR PFC IO
IO configuration is not complete – the drive is unable to allocate a digital
input (interlock) for each PFC motor (parameters 8120
8127
MOTORS
PAR USER
The user defined U/f ratio is not compatibility (only when parameters 2605
/
DEFINED U
F
= 3 ).
See Parameter Group 37.
PAR USER LOAD
C
Description and Recommended Corrective Action
4...6 have non-zero values.
RELAY OUTPUTS
= 0.
COMM PROT SEL
/ 9908
MOTOR NOM FREQ
/
MOTOR NOM SPEED
/ Motor Poles) < 0.992
MOTOR NOM FREQ
AUTOCHNG INTERV
) does not match the PFC motors in Group 14
MOTORS
.
AUTOCHNG INTERV
).
1
= 10
EXT
COMMANDS
< 16
MOTOR NOM SPEED
NR OF AUX
.
and
INTERLOCKS
Diagnostics
201