Code Description
1609 START ENABLE 2
Selects the source of the start enable 2 signal.
Note: Start enable functionality differs from the run enable functionality.
0 =
– Allows the drive to start without an external start enable signal.
NOT SEL
1 =
1 – Defines digital input DI1 as the start enable 2 signal.
DI
• This digital input must be activated as the start enable 2 signal.
• If the voltage drops and de-activates this digital input, the drive will coast to stop and show alarm 2022 on panel
display. The drive will not start until start enable 2 signal resumes.
2...6 =
2...
6 – Defines digital input DI2...DI6 as the start enable 2 signal.
DI
DI
• See DI1 above.
7 =
– Assigns the fieldbus Command Word as the source for the start enable 2 signal. Bit 3 of the Command
COMM
word 2 (parameter 0302) activates the start disable 2 signal.
• See fieldbus user's manual for detailed instructions.
(-1) =
1(
) – Defines an inverted digital input DI1 as the start enable 2 signal.
DI
INV
(-2)...(-6) =
2(
)...
DI
INV
• See
1 (
) above.
DI
INV
1610 DISPLAY ALARMS
Controls the visibility of the following alarms:
• 2001, Overcurrent alarm
• 2002, Overvoltage alarm
• 2003, Undervoltage alarm
• 2009, Device overtemperature alarm
0 =
– The above alarms are suppressed.
NO
1 =
– All of the above alarms are enabled.
YES
Start-Up
Supplied from China by: Guangzhou Tofee Electro Mechanical Equipment Co., Ltd
Email: info@tofee.com.cn
6(
) – Defines an inverted digital input DI2...DI6 as the start enable 2 signal.
DI
INV
ACS510 User's Manual