ACS510 User's Manual
Fuses, 380...480 V Drives
ACS510-01-
see below
-03A3-4
-04A1-4
-05A6-4
-07A2-4
-09A4-4
-012A-4
-017A-4
-025A-4
-031A-4
-038A-4
-046A-4
-060A-4
-072A-4
-088A-4
-125A-4
-157A-4
-180A-4
-195A-4
-246A-4
-290A-4
Emergency Stop Devices
The overall design of the installation must include emergency stop devices and any
other safety equipment that may be needed. Pressing STOP on the drive's control
panel does NOT:
• Generate an emergency stop of the motor.
• Separate the drive from dangerous potential.
Input Power Cables/ Wiring
Input wiring can be any of:
• A four conductor cable (three phases and ground/protective earth). Shielding is
not required.
• Four insulated conductors routed through conduit.
Size wiring according to local safety regulations, appropriate input voltage and the
drive's load current. In any case, the conductor must be less than the maximum limit
defined by the terminal size (see "Drive's Power Connection Terminals" on page
218).
Supplied from China by: Guangzhou Tofee Electro Mechanical Equipment Co., Ltd
Email: info@tofee.com.cn
Input Current
A
IEC 269 gG (A)
3.3
10
4.1
5.6
7.2
9.4
11.9
16
17
25
25
31
35
38
50
46
60
63
72
80
88
125
125
160
157
200
180
250
205
250
245
250
290
315
Input power (mains) fuses
UL Class T (A)
Bussmann Type
10
JJS-10
15
JJS-15
20
JJS-20
30
JJS-30
40
JJS-40
50
JJS-50
60
JJS-60
80
JJS-80
90
JJS-90
125
JJS-125
175
JJS-175
200
JJS-200
250
JJS-250
250
JJS-250
250
JJS-250
315
JJS-350
215
Technical Data