70
0305 FAULT WORD 1
Read-only copy of the Fault Word 1.
• When a fault is active, the
corresponding bit for the active fault
is set in the Fault Words.
• Each fault has a dedicated bit
allocated within Fault Words.
• See "Fault Listing" on page 197 for a
description of the faults.
• The control panel displays the word
in hex. For example, all zeros and a 1
in Bit 0 displays as 0001. All zeros
and a 1 in Bit 15 displays as 8000.
0306 FAULT WORD 2
Read-only copy of the Fault Word 2.
See parameter 0305.
0307 FAULT WORD 3
Read-only copy of the Fault Word 3.
See parameter 0305.
0308 ALARM WORD 1
• When an alarm is active, the
corresponding bit for the active alarm
is set in the Alarm Words.
• Each alarm has a dedicated bit
allocated within Alarm Words.
• Bits remain set until the whole alarm
word is reset. (Reset by writing zero
to the word.)
• The control panel displays the word
in hex. For example, all zeros and a 1
in Bit 0 displays as 0001. All zeros
and a 1 in Bit 15 displays as 8000.
0309 ALARM WORD 2
See parameter 0308.
Start-Up
Supplied from China by: Guangzhou Tofee Electro Mechanical Equipment Co., Ltd
Email: info@tofee.com.cn
Bit # 0305,
1 0306,
FAULT WORD
0
OVERCURRENT
1
DC OVERVOLT
2
DEV OVERTEMP
3
SHORT CIRC
4
Reserved
5
DC UNDERVOLT
6
AI1 LOSS
7
AI2 LOSS
8
MOT OVERTEMP
9
PANEL LOSS
10
Reserved
11
MOTOR STALL
12
CB OVERTEMP
13
EXT FAULT 1
14
EXT FAULT 2
15
EARTH FAULT
Bit #
0308,
ALARM WORD
0
OVERCURRENT
1
OVERVOLTAGE
2
UNDERVOLTAGE
3
DIRLOCK
4
COMM LOSS
5
AI1 LOSS
6
AI2 LOSS
7
PANEL LOSS
8
DEVICE OVERTEMP
9
MOTOR TEMP
10
Reserved
11
MOTOR STALL
12
AUTORESET
13
PFC AUTOCHANGE
14
PFC ILOCK
15
Reserved
ACS510 User's Manual
2 0307,
FAULT WORD
Obsolete
EFB 1
THERM FAIL
EFB 2
OPEX LINK
EFB 3
OPEX PWR
INCOMPATIBLE SW
CURR MEAS
USER LOAD CURVE
SUPPLY PHASE
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
DRIVE ID
Reserved
CONFIG FILE
System error
SERIAL 1 ERR
System error
EFB CON FILE
System error
FORCE TRIP
System error
MOTOR PHASE
System error
OUTP WIRING
Param. setting fault
1
0309,
ALARM WORD
OFF BUTTON
PID SLEEP
Reserved
Reserved
START ENABLE 1
START ENABLE 2
EMERGENCY STOP
Reserved
Reserved
Reserved
USER LOAD CURVE
START DELAY
Reserved
Reserved
Reserved
Reserved
3
FAULT WORD
2