ABB ACS510-01 User Manual page 213

Low voltage ac drives
Table of Contents

Advertisement

ACS510 User's Manual
Derating
The load capacity (current and power) decreases for certain situations, as defined
below. In such situations, where full motor power is required, oversize the drive so
that the derated value provides sufficient capacity.
For example, if your application requires 15.4 A of motor current and a 8 kHz
switching frequency, calculate the appropriate drive size requirement as follows:
The minimum size required = 15.4 A / 0.80 = 19.25 A
Where: 0.80 is the derating for 8 kHz switching frequency (see "Switching Frequency Derating"
below).
Referring to I
requirement of 19.25 A: ACS510-01-025A-4.
Temperature Derating
In the temperature range +40 °C
is decreased 1% for every 1 °C (1.8 °F) above +40 °C (+104 °F). The output current
is calculated by multiplying the current given in the rating table by the derating factor.
Example If the ambient temperature is 50 °C (+122 °F) the derating factor is
100% - 1%/°C x 10 °C
The output current is then 0.90 x I
Altitude Derating
In altitudes 1000
every 100 m (330 ft). If the installation site is higher than 2000 m (6600 ft) above sea
level, please contact your local ABB distributor or office for further information.
Switching Frequency Derating
If the 8 kHz switching frequency (parameter 2606) is used, either:
• Derate P
• Set parameter 2607
switching frequency if/when the drive's internal temperature exceeds 90 °C. See
the parameter description for 2607 for details.
If the 12 kHz switching frequency (parameter 2606) is used, either:
• Derate P
(86 °F), or
• Set parameter 2607
switching frequency if/when the drive's internal temperature exceeds 80 °C. See
the parameter description for 2607 for details.
Supplied from China by: Guangzhou Tofee Electro Mechanical Equipment Co., Ltd
Email: info@tofee.com.cn
in the ratings tables (page 211), the following drives exceed the I
2N
50 °C (+104 °F
...
90% or 0.90.
=
2N
4000 m (3300
13,200 ft) above sea level, the derating is 1% for
...
...
and I
to 80% or
N
2N
SW FREQ CTRL
and I
to 65%, and derate ambient temperature maximum to 30 °C
N
2N
SW FREQ CTRL
122 °F) the rated output current
...
.
= 1 (
) which allows the drive to reduce the
ON
= 1 (
) which allows the drive to reduce the
ON
213
2N
Technical Data

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents

Save PDF