Code Description
0135 COMM VALUE 1
Free data location that can be written from serial link.
0136 COMM VALUE 2
Free data location that can be written from serial link.
0137 PROCESS VAR 1
Process variable 1
Defined by parameters in Group 34: Panel Display.
0138 PROCESS VAR 2
Process variable 2
Defined by parameters in Group 34: Panel Display.
0139 PROCESS VAR 3
Process variable 3
Defined by parameters in Group 34: Panel Display.
0140 RUN TIME
The drive's accumulated running time in thousands of hours (kh). Cannot be reset.
0141 MWH COUNTER
The drive's accumulated power consumption in megawatt hours. Can not be reset.
0142 REVOLUTION CNTR
The motor's accumulated revolutions in millions of revolutions.
Can be reset by pressing UP and DOWN keys simultaneously when the control panel is in the Parameters mode.
0143 DRIVE ON TIME HI
The drive's accumulated power-on time in days. Cannot be reset.
0144 DRIVE ON TIME LO
The drive's accumulated power on time in 2 second ticks (30 ticks = 60 seconds). Cannot be reset.
0145 MOTOR TEMP
Motor temperature in degrees Celsius / PTC resistance in ohms.
Applies only if motor temperature sensor is set up. See parameter 3501.
0146
NOT USED
...
0148
0149 OVERRIDE ACTIVED
Override mode actived recorder.
1 = Drive is in override mode. Parameter setting or drive control is not possible. Please see paramerter group 17.
0 = Drive is in normal operating mode (in override mode).
Note! If override mode actived, this ACS510 module is out of warranty.
0150 CB TEMP
Temperature of the drive control board in degrees Celsius/Fahrenheit.
Note: Some drives have a control board (OMIO) that does not support this feature. These drives always show the
constant value of 25.0 °C.
0151 INPUT KWH (R)
Calculated actual intake energy in kWh.
Can be reset by pressing UP and DOWN keys simultaneously when the control panel is in the Parameters mode.
0152 INPUT MWH
Calculated actual intake energy in MWh.
0158 PID COMM VALUE 1
Data received from fieldbus for PID control (PID1 and PID2).
0159 PID COMM VALUE 2
Data received from fieldbus for PID control (PID1 and PID2).